Input Signal Delay,
On to Off
30 ms max
Field Power Dissipation
3.9VA @ rated current
Isolation Voltage
120V ac (continuous), reinforced insulation type,
tested at 1250V ac for 60 s, I/O to system
Environmental - Common To All Base Blocks in This Publication
Attribute
Value
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0...55 °C (32...131 °F)
Storage Temperature
IEC60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
IEC60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
IEC60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock)
-40...85 °C (-40...185 °F)
Relative Humidity
IEC60068-2-30
(Test Db, Unpackaged Damp Heat)
5...90% noncondensing
North American Temp Code
T5
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock Operating
IEC60068-2-27 (Test Ea, Unpackaged Shock) 10 g
Shock Non-operating
IEC60068-2-27 (Test Ea, Unpackaged Shock) 30 g
Emissions
CISPR 11: Group 1, Class A
ESD Immunity
IEC6100-4-2
8 kV air discharges
Radiated RF Immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80%AM from 80…1000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz