Specifications for the various inputs and outputs are provided below.
1
Use TB2-5 for shield connection.
2
Refer to Typical Isolation diagram below.
I/O Type
Configuration
Specification
Ref.
Standard
0-10V Input
100k ohm input impedance.
TB2-4
1
0-10V Output
Can drive a 10k ohm load (60 mA short circuit
current limit).
TB2-9
1
0-20 mA Input
200 ohm input impedance.
TB2-4
1
10k Ohm Pot. Input 760k ohm input impedance.
Pot. source = 5V through 2.67k ohms to TB2-1.
TB2-4
1
Option
Board
2
0-10V Input
100k ohm input impedance.
TB2-5
0-10V Output
Can drive 3.3k ohms (3 - parallel 10k ohm loads). TB2-5
0-20 mA Input
100 ohm input impedance.
TB2-5
0-20 mA Output
Can drive 400 ohms (3 - series 0-20 mA inputs). TB2-5
Pulse Input
250 ohms in series with an opto LED.
Pulse high is greater than 8 mA or 3.6V, while
pulse low is less than 0.8V or 0.2 mA.
Absolute maximum continuous input level is 12V
or 50 mA.
TB2-9
Pulse Output
Provides a current limited 4.5V square wave.
This output can drive one PLUS or three PLUS II
pulse inputs.
TB2-5
Thermistor Input
5V across 3.3k ohms in series with the
thermistor.
This arrangement limits the measuring voltage to
less than 2.5V (no self-heating).
TB2-4
Signal
Conditioning
Signal
Option Board
User
I/O
Power
Typical Isolation
True Galvanic Isolation to 200V AC
(greater than 10 M ohm, less than 50 pf).
Rockwell Automation helps its customers receive a superior return on their investment by bringing
together leading brands in industrial automation, creating a broad spectrum of easy-to-integrate
products. These are supported by local technical resources available worldwide, a global network
of system solutions providers, and the advanced technology resources of Rockwell.
Worldwide representation.
Argentina • Australia • Austria • Bahrain • Belgium • Bolivia • Brazil • Bulgaria • Canada • Chile • China, People’s Republic of • Colombia • Costa Rica • Croatia • Cyprus
Czech Republic • Denmark • Dominican Republic • Ecuador • Egypt • El Salvador • Finland • France • Germany • Ghana • Greece • Guatemala • Honduras • Hong Kong
Hungary • Iceland • India • Indonesia • Iran • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Macau • Malaysia • Malta • Mexico
Morocco • The Netherlands • New Zealand • Nigeria • Norway • Oman • Pakistan • Panama • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia
Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic of • Spain • Sweden • Switzerland • Taiwan • Thailand • Trinidad • Tunisia • Turkey • United Arab Emirates
United Kingdom • United States • Uruguay • Venezuela
Rockwell Automation Headquarters, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414 382-2000, Fax: (1) 414 382-4444
Publication 1336 PLUS-5.70 – July, 1998
P/N 189357 (02)
Supersedes January, 1998
Copyright 1998 Rockwell International Corporation. All rights reserved. Printed in USA.