beautypg.com

Ds200 installation – Rockwell Automation 1397 200-300HP AC Line Disconnect Inst. User Manual

Page 4

background image

1397 300HP AC Line Disconnect

4

1397-5.27 October, 1997

TORQUE

14-10GA 35 LB.-IN.

0 GA 48 LB.-IN.

SPEC

GND

!

DANGER

RISK OF ELECTRICAL SHOCK. DISCONNECT INPUT
POWER BEFORE SERVICING EQUIPMENT.

P/N 33145

DANGER

CIRCUIT BREAKER DOES NOT DISCONNECT INCOMING A0
LINE POWER IT ONLY PROVIDES DC FAULT PROTECTION.

LE DISCONECTEUR NE COUPTE PAS L'AUTOMENTATION DU SPOTEUR IL NES
SERT QUE A ASSURER UNE PROTECTION CONTRE LES DESFAULTS DC.

810903-2424

283

282

281

4FU 5FU 6FU 7FU 8FU

183

182

181

RISK OF SHOCK

REPLACE AFTER

SERVICING

DANGER

!

Plastic

Line Fuse

Cover

ON

81

82

83

OFF

M10 Nut

and Washer

Removed

Previously

M10 Nut

and Washer

Removed

Previously

M10 Nut

and Washer

Removed

Previously

Left

Bus Bar

Right

Bus Bar

Center

Bus Bar

Line Side

Label

3/8"
Flat Washer
3/8" Split
Lockwasher
3/8" x 3/4" Bolt
— (3) Places —

7a

Remove the disconnect’s bottom lug cover by loosening the (2)
screws holding it in place. Put one split lockwasher and one flat
washer onto each of the bolts used to fasten the bus bars to the
disconnect.

DS200 Installation

7b

Attach one angled bus bar to
the drive’s left line fuse
connector and the
disconnect’s left load
connector. The leg of the bus
bar attaches to the

disconnect. The foot of

the bus bar faces left

and it’s bolt hole

slips over the lug
for the line fuse
connector. Use

one of the bolt,

lockwasher and flat

washer 3/8" assemblies

to fasten the bus bar to the
disconnect

7c

Attach the straight bus bar to
the drive’s center line fuse
connector and the
disconnect’s center
connector. Use one of the
bolt, lockwasher and flat
washer 3/8" assemblies to
fasten the bus bar to the
disconnect.

7d

Attach the remaining angled bus bar to the drive’s right line fuse connector and the disconnect’s right load
connector. The leg of the bus bar attaches to the disconnect. The foot of the bus bar faces right and its bolt
hole slips over the lug for the line fuse connector. Use one of the bolt, lockwasher, and flat washer 3/8"
assemblies to fasten the bus bar to the disconnect.

7e

Fasten the bus bars to the drive’s line fuse connectors with the M10 nuts and washers removed in

Step 1

.

• Tighten the bolts fastening the bus bars to the disconnect to 23N-m (200lb.-in.).

• Tighten the nuts fastening the bus bars to the line fuse connectors to 23N-m (200lb.-in.).