Rockwell Automation 1606-XLERED Power Supply Reference Manual User Manual
Page 8
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
8
Rockwell Automation Publication 1606-RM033A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
10. EMC
This redundancy module is suitable for applications in industrial environment as well as in residential, commercial and
light industry environment without any restrictions (e.g. cable length). The CE Mark indicates conformance with EMC
directive 2004/108/EC and the low-voltage directive (LVD) 2006/95/EC.
A detailed EMC report is available upon request.
EMC Immunity
According generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field
EN 61000-4-3
80MHz-2.7GHz
10V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Input lines
Output lines
Alarm contacts
2kV
2kV
2kV
Criterion A
Criterion A
Criterion A
Surge voltage on
input lines
EN 61000-4-5
+ -
+/
- Chassis ground
200V
1kV
Criterion A
Criterion A
Surge voltage on
output lines
EN 61000-4-5
+ -
+/
- Chassis ground
200V
1kV
Criterion A
Criterion A
Surge voltage on
alarm contacts
EN 61000-4-5
Alarm contact Chassis ground
1kV
Criterion A
Conducted disturbance
EN 61000-4-6
0.15-80MHz
10V
Criterion A
Power-frequency magnetic
field *)
EN 61000-4-8
50Hz
30A/m
Criterion A
Criteria:
A: Redundancy module shows normal operation behavior within the defined limits.
Notes:
*) A test is not applicable according to EN 61000-6-2, since the device does not contain components susceptible to magnetic fields, e.g. hall
elements, electrodynamic microphones, etc.
EMC Emission
According generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
Class B, input lines *)
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
Class B, output lines *)
Radiated emission
EN 55011, EN 55022
Class B
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
*)
Provided that power sources connected on the inputs fulfill the class B requirements as well.