1305 series c parameter list – Rockwell Automation 1305 FRN. 6.XX Reference Guide User Manual
Page 6
6
Rockwell Automation Publication 1305-5.2.2 - September 2013
1305 Adjustable Frequency AC Drive
1305 Series C Parameter List
Speed Indicator
LEDs
(only available
with digital
speed control)
Illuminates in steps to give an approximate visual indication of the commanded speed.
If the Analog Speed Potentiometer option has been ordered, the Increment/Decrement keys
and Speed Indicator LEDs will be replaced by the pot.
Item
Name
Description
Group/
Parameter
No.
Units
Min.
Value
Max.
Value
Default
Value
Group/
Parameter
No.
Units
Min.
Value
Max.
Value
Default
Value
Metering
Analog Invert
84
Text
—
—
Disabled
Output Current
54
0.01 Amps
0.00
2x Drive Output Current
—
4-20 mA Loss Sel
81
Text
—
—
Stop/Fault
Output Voltage
1
1 Volt
0
Maximum Voltage
—
Stop Select
10
Text
—
—
Ramp
Output Power
23
0.01 kW
0.00
2x Rtd. Dr. Output Power —
DC Hold Time
12
0.1 Sec
0.0
150.0
0.0
DC Bus Voltage
53
1 Volt
0
410…230V Drive
DC Hold Volts
13
1 Volt
0
25% of Max DRV
0
815…460V Drive
—
DB Enable
11
Text
—
—
Disabled
Output Freq.
66
0.01 Hz
0.00
Maximum Frequency
—
Motor Type
41
Text
—
—
Induc/Reluc
Freq. Command
65
0.01 Hz
0.00
+400.00
0.00
Compensation
52
Text
—
—
Comp
MOP Hz
42
0.01 Hz
0.00
400.00
—
Frequency Set
Drive Temp
70
1 deg. C
0
100
—
Freq Select 1
5
Text
—
—
Adapter 1
Last Fault
4
Numeric
0
Max. Fault No.
—
Freq Select 2
6
Text
—
—
Remote Pot
% Output Power
3
1%
0
200% Drive Rated Power —
Jog Frequency
24
0.1 Hz
0.0
400.0
10.0
% Output Curr.
2
1%
0
200% Rtd. Dr. Out. Curr.
—
Prst/2nd Accel
26
Text
—
—
Preset
Setup
Upper Presets
72
Text
—
—
Disabled
Input Mode
21
Text
(1)
—
—
Three Wire
Accel Time 2
30
0.1 sec
0.0
3600.0
5.0
Freq Select 1
5
—
—
Adapter 1
Decel Time 2
31
0.1 sec
0.0
3600.0
5.0
Accel Time 1
7
0.1 sec
0.0
3600.0
10.0
Preset Freq 1
27
0.1 Hz
0.0
400.0
10.0
Decel Time 1
8
0.1 sec
0.0
3600.0
10.0
Preset Freq 2
28
0.1 Hz
0.0
400.0
20.0
Base Frequency
17
1 Hz
40
400
60
Preset Freq 3
29
0.1 Hz
0.0
400.0
30.0
Base Voltage
18
1 Volt
25% of DRV 100% of Max DRV
Max DRV
Preset Freq 4
73
0.1 Hz
0.0
400.0
40.0
Maximum Voltage 20
1 Volt
25% of DRV 110% of Max DRV
Max DRV
Preset Freq 5
74
0.1 Hz
0.0
400.0
50.0
Minimum Freq
16
1 Hz
0
120
0
Preset Freq 6
75
0.1 Hz
0.0
400.0
60.0
Maximum Freq
19
1 Hz
40
400
60
Preset Freq 7
76
0.1 Hz
0.0
400.0
0.0
Stop Select
10
—
—
Ramp
Skip Freq 1
32
1 Hz
0
400
400
Current Limit
36
1%
20% of DRC 150% of DRC
150% of DRC
Skip Freq 2
33
1 Hz
0
400
400
Overload Mode
37
Text
—
—
No Derating
Skip Freq 3
34
1 Hz
0
400
400
Overload Current
38
0.1 Amps
20% of DRC 115% of DRC
115% of DRC
Skip Freq Band
35
1 Hz
0
15
0
Sec Curr Limit
141
1%
0% of DRC
150% of DRC
0% of DRC
MOP Increment
22
1 Hz/Sec
0.00
255.00
1.00
Adaptive I Lmt
149
—
—
Enabled
Analog Filter
144
Text
—
—
100%
Advanced Setup
Feature Select
Minimum Freq
16
1 Hz
0
120
0
Run On Power Up
14
Text
—
—
Disabled
Maximum Freq
19
1 Hz
40
400
60
Reset/Run Tries
85
Numeric
0
9
0
Base Frequency
17
1 Hz
40
400
60
Reset/Run Time
15
0.1 Sec
0.5
30.0
1.0
Base Voltage
18
1 Volt
25% of DRV 100% of Max DRV
Max DRV
S Curve Enable
57
Text
—
—
Disabled
Break Frequency
49
1Hz
0
120
30
S Curve Time
56
0.1 Sec
0.0
300.0
0.0
Break Voltage
50
1 Volt
0
50% of Max DRV
Dr. Size Dep.
Language
47
—
—
Approp. Lang.
Maximum Voltage 20
1 Volt
25% of DRV 110% of Max DRV
Max DRV
Cable Length
143
Text
—
—
Short
DC Boost Select
9
Text
—
—
Break Point
Rated Slip
146
0.1 Hz
0.0
5.0
2.0
Start Boost
48
1 Volt
0
25% of Max DRV
Dr. Size Dep.
Slip Comp Adder
148
0.01 Hz
0.00
5.00
—
Run Boost
83
1 Volt
0
25% of Max DRV
0
IR Comp %
147
1%
0%
150%
Drv. Depend.
PWM Frequency
45
0.1 kHz
2.0
8.0
4.0
(Table continued on next page.)