Terminal block tb2 designations, Tb2 terminal descriptions – Rockwell Automation 1305 FRN. 6.XX Reference Guide User Manual
Page 3

Rockwell Automation Publication 1305-5.2.2 - September 2013
3
1305 Adjustable Frequency AC Drive
Terminal Block TB2
Designations
See footnotes below.
TB2 Terminal Descriptions
➀
Required to operate drive. STOP also used to clear a fault.
➁
Use HIM Stop button to clear faults.
➂
Contact Closure Input. Internal 5V supply. Do not apply external voltage.
➃
When the ENABLE signal is lost, the drive output immediately shuts off and the motor will coast to a stop.
➄
A Start command will override any Jog command.
➅
See 1305 User Manual, publication 1305-5.2, for input configurations based on the setting of parameter 21 - [Input Mode].
Remote Pot
1
2
3
4
5
6
7
8
9
10
Source
Wiper or 0-10V DC Input
Common
4-20mA Input
0-10V Output
0-10V
Common
Stop
➂
Start
➂
Output #1
➄
➀➃
➀
24VDC Source
(User Supplied)
11
12
13
14
15
16
17
18
19
20
Enable
➂
Common
Reverse
➂
Jog
➂
Common
SW2
➂➅
SW3
➂➅
SW1
➂➅
(Sink)
Output #2
User Side
Remote Pot
Run Forward
Run Reverse
Jumper
➀➁
Jumper
➀➃
1
2
3
4
5
6
7
8
9
10
Source
Wiper or 0-10V DC Input
Common
4-20mA Input
0-10V Output
0-10V
Common
Stop
➂
User Side
Start
➂
Output #1
24VDC Source
(User Supplied)
11
12
13
14
15
16
17
18
19
20
Enable
➂
Common
Reverse
➂
Jog
➂
Common
SW2
➂➅
SW3
➂➅
SW1
➂➅
(Sink)
Output #2
General Three Wire
General Run Fwd/Rev
Terminals
Signal
Specification
1, 2, 3
External Speed Potentiometer
10 k
Ω Potentiometer, 2 watts
2, 3
0…10V Analog Input
Drive Input Impedance = 100 k
Ω
4, 3
4…20 mA Analog Input
Drive Input Impedance = 250
Ω
5, 3
0…10V Analog Output
Meter Impedance
≥ 4 kΩ
6, 7
Start
Contact Closure Input ➂
8, 7
Stop
Contact Closure Input ➂
9, 10
Programmable Output 1
Resistive Rating = 115V AC/30V DC, 5A
Inductive Rating = 115V AC/30V DC, 2A
11, 12
Drive Enable
Contact Closure Input ➂ ➃
13, 12
Reverse
Contact Closure Input ➂
14, 15
Jog
Contact Closure Input ➂
16, 15
SW1
Contact Closure Input ➂
17, 15
SW2
Contact Closure Input ➂
18, 15
SW3
Contact Closure Input ➂
19, 20
Programmable Output 2
24V DC ± 20%, 50 mA max (sink)