Environment – Rockwell Automation 1606-XLSBUFFER24 Power Supply Reference Manual User Manual
Page 9
![background image](/manuals/578837/9/background.png)
All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM026A-EN-P — April 2014
9
Bulletin 1606 Switched Mode Power Supplies
14. EMC
The unit is suitable for applications in industrial environments as well as in residential, commercial and light industry
environments without any restriction. The CE Mark is in conformance with EMC guidelines 89/336/EEC and 93/68/EEC and
the low-voltage directive (LVD) 73/23/EWG.
A detailed EMC Report is available on request
EMC Immunity
EN 61000-6-1 EN 61000-6-2
Generic standards
Electrostatic discharge 1)
EN 61000-4-2
Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field
EN 61000-4-3 80MHz-1GHz
10V/m
Criterion
A
Fast transients (Burst)
EN
61000-4-4
2kV Criterion
A
Surge voltage
EN 61000-4-5
+ -
+ / - housing
500V
500V
Criterion A
Criterion A
Conducted disturbance
EN 61000-4-6
0,15-80MHz
10V
Criterion A
1)
Grounded on the DIN rail
EMC Emission
EN 61000-6-3 and EN 61000-6-4
Generic standards
Conducted emission
EN 55022
Class B
Radiated emission
EN 55011, EN 55022
Class B
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
15. Environment
Operational temperature
-25°C to +70°C
full power
Storage temperature
-40 to +
85°C
storage and transportation
Humidity
5 to 95% r.H.
no condensation allowed
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
IEC 60068-2-6
Vibration random
0.5m
2
(s
3
)
IEC 60068-2-64
Shock
30g 6ms, 20g 11ms
IEC 60068-2-27
Altitude
0 to 6000m
All approvals apply only up to 2000m
Over-voltage category
III
EN 50178
II
EN 50178 above 2000m altitude
Degree of pollution
2
EN 50178, not conductive
The ambient temperature is defined 2cm below the unit.