Buffer mode – Rockwell Automation 1606-XLSBUFFER24 Power Supply Reference Manual User Manual
Page 5
![background image](/manuals/578837/5/background.png)
All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM026A-EN-P — April 2014
5
Bulletin 1606 Switched Mode Power Supplies
7. Buffer Mode
Rated output current
nom.
20A
Current limitation
min.
20A
Electronically limited
Output voltage
typ.
22.5V
Jumper in position “22.5V fixed”
typ.
1V below input
voltage
Jumper in position “Vin –1V”
Ripple and noise voltage
max.
200mVpp
20Hz to 20MHz, 50Ohm
Hold-up time
min.
0.2s
22.5V, 20A
typ. 0.31s
22.5V,
20A
min. 28s
22.5V,
0.1A
typ. 43s
22.5V,
0.1A
To increase buffer current or extend hold-up time, any given number of buffer
units can be installed in parallel.
Activation threshold
typ.
22.5V
Ju
mper in position “22.5V fixed”
Buffering starts if terminal voltage falls below 22.5V.
typ.
Vin –1V
Jumper in position “Vin –1V”
Buffering starts if the terminal voltage decreases by
more than 1V. Buffering ends when terminal voltage
increases by more than 1V
Voltage changes slower than 0.54V/s will be ignored
unless the voltage is above 22.5V. Below 22.5V
buffering starts immediately.
Status lamp
flashes 10Hz
Active signal
low ohmic
Ready signal
high ohmic
Fig. 7-1 Hold-up time
0,1 A
1,0 A
10,0 A
100,0 A
0,1 s
1,0 s
10,0 s
100,0 s
Buffer
Current
typ. ( 22,5 V )
typ. ( 27,8 V )
min. ( 22,5 V )