Operation, maintenance and troubleshooting, User controls and indicators, Led indicators – Rockwell Automation 1608S I-Sense User Manual User Manual
Page 16: Table 3 - green normal led flash codes, Table 4 - red error led flash codes

Rockwell Automation Publication 1608S-UM001A-EN-P - July 2013
16
Operation, Maintenance and Troubleshooting Chapter 4
Operation, Maintenance and Troubleshooting
The left-side cover may be removed at any time to access the
communications ports.
User controls and indicators
These user controls and indicators are available:
•
The i-Sense Management Console (requires an Ethernet connection
to i-Sense)
•
The www.igrid.com website (available from any Web browser)
•
Red and Green LED indicators (see Table 3 and Table 4 below)
•
RESET push button (located inside left cover)
•
Heartbeat
♡
push button (located inside left cover)
LED indicators
The LEDs will flash to indicate status; the flash codes are listed in the tables
below. Additional status information is available by connecting to the i-Sense
Management Console via the Ethernet port.
Startup/Confirmation Blink:
At power-up and to confirm a push-button
operation, both LEDs will blink rapidly for a few seconds
Table 3 -
Green NORMAL LED
Flash Codes.
Table 4 -
Red ERROR LED
Flash Codes.
Flash
Rate
Meaning
Off
No Power
1
OK
2
Voltage events captured, waiting to transmit.
3
Voltage deviation event detected, voltage has not yet returned to normal (PQ event in progress).
4
Establishing connection to the i-Grid servers.
5
Connected to the i-Grid servers, uploading PQ event data.
Constant
Not operating properly. Push RESET button
Flash Rate
Meaning/Possible Causes
Off
OK
1
Communication error on the last attempt to contact the i-Grid servers. Will retry the connection after a period of time
2
Ethernet interface is not configured and connected to a network
Ethernet interface is initializing
Network cable is unplugged
Note: Only in Ethernet mode
3
Voltage is low. The i-Sense has not detected an AC signal above 90% nominal on each of the enabled voltage channels
4
Both Ethernet and event detection are not initialized yet (combination of status 2 and 3) Note: Only in Ethernet mode