Installation Chapter 3
Communications
Connections
1.
Remove left side cover (two Phillips-head screws, top and bottom)
2.
Conduit entry: top or bottom.
3.
Install appropriate communications cable(s) (See
Communications Settings on page 6
8P8C (RJ45) modular Ethernet cable. Pass the Ethernet cable
through the included RF filter core, and close the core securely, as
. Failure to install the cable filter may result in RF
emissions beyond the standards of the EU’s EMC Directive.
RJ11 telephone line (analog PSTN)
Figure 2 - Ethernet cable filter installation. The clip-on filter core is supplied with the i-sense.
Final Check
• Check all connections
• Replace left and right side covers
External Power Supply
The external 9V DC power supply (not provided) is used only during
configuration; it should not be used in normal operation. Remove the
left-side cover to access the 9Vdc jack
Initial Battery Charge Time
The rechargeable batteries may become discharged after some time
on the shelf. Allow 30 minutes charge time after power-up
before the i-Sense is ready to record voltage interruption events.