Installation Chapter 3
Installation
Pre-installation
1.
Inspect for shipping damage
2.
Record the i-Sense serial number (See
3.
Register the i-Sense at www.igrid.com (See
)
4.
Configure the i-Sense hardware for the service voltage (See
)
5.
Configure communications software using the Ethernet port. (this can be
done after installation and power-up)
Environmental Conditions
The i-Sense is rated for installation in the following environment:
•
Indoor use only, no conductive pollution.
•
Altitude up to 2000 m (6500 ft)
•
Temperature range +0...+40 °C (+32...+104 °F)
•
Maximum relative humidity 95%, non-condensing.
Mounting
•
Provide 10 inches (250 mm) clearance around the i-Sense for cooling and
access.
•
Remove the left and right covers (four Phillips-head screws, two top and
two bottom)
•
Mount the i-Sense to a vertical surface using the four mounting holes. Two
of the four mounting screws should penetrate into studs at least 1 in.
(25 mm). Mounting screws 1.5 in. (38 mm) long are recommended.
Electrical Connections
•
Branch protection: upstream fuse or circuit breaker protection rated 20A
or less is required. Protection rated less than 5 A is not recommended.
•
Conduit entry: top or bottom.
•
Connect the Ground (Earth) wire to the #10-32 stud near the bottom
knock-out.
•
Connect mains line to the INPUT_1 terminal block, according to the
proper wiring diagram from Table 2.
•
6-Channel Version: if the INPUT_2 terminal block is present, wire the
second 3-phase set using the same wiring diagram.
•
Verify that the JP1 plug is properly configured, per Table 1: The plug with
RED wires must be installed if the channel voltage is greater than 250
VAC.
•
Replace the right-side cover and two screws
WARNING: Do not apply power to the i-Sense until the wiring is completed
and right-side cover is replaced. Installation must be performed by an
electrician, in accordance with all local and national codes.
WARNING: This unit is not rated for 600V AC or 690V AC L-L installations.
600Y/346V installations require 4-wire L-N wiring method. The neutral must be
connected as shown in Table 2.