beautypg.com

Front, Faults (continued), 1336 plus adjustable frequency ac drive w – Rockwell Automation 1336S ADJ FREQ AC DRIVE User Manual

Page 4

background image

ATTENTION: This publication is designed as a reference
tool. The 1336 PLUS User Manual (publication 1336
PLUS-5.0) must be consulted for more detailed informa-
tion about parameters, faults and hazards of personal
injury.

1336 PLUS Adjustable
Frequency AC Drive w/

Reference Guide

Overload Fault

Excessive motor load exists. Reduce it

07

so output current does not exceed %
current set by the [Overload Current].

Overtemp Fault

Check for blocked or dirty heat sink

08

fins. Ambient temperature must not
exceed 40

°

C (104° F).

Overvolt Fault

Monitor AC line for high line voltage or

05

transient conditions. Can also be
caused by motor regeneration. Extend
decel time or install dynamic brake.

Phase U, V, W Fault

Check wiring between drive and motor.

38, 39, 40

Check motor for grounded phase.

P Jump Err Flt

Reserved for future use.

37

Poles Calc Flt

Calculated value of [Motor Poles] must

50

be between 2 and 32. Check program-
ming of [Motor NP RPM] & [Motor NP
Hertz].

Power Loss Fault

Monitor the incoming AC line for low

03

voltage or line power interruption.

Power Mode Fault

Check all connections to the Control

26

Board/Language Module.

Power Overload

2

Drive rating of 150% for 1 minute has

26

been exceeded. Reduce load.

Power Test Flt

Internal power mode variable received

46

incorrect value. Check Power/Driver Bd.

Precharge Fault

Check the precharge circuit.

19

Precharge Open

Check the precharge circuit.

56

Reprogram Fault

Occurs after drive has been reset to

48

factory default values. Clear fault or
cycle drive power. Reprogram.

ROM or RAM Flt

Internal ROM/RAM tests failed. Check

68

Language Module.

Run Boost Fault

[Run Boost] set greater than [Start

34

Boost]. Verify correct programming.

Serial Fault

Check for break in communications

10

line.

Shear Pin Fault

2

Programmed [Current Limit] exceeded

63

& [Shear Pin Fault] enabled. Check load
requirements & {Current Limit] setting.

Temp Sense Open

Heat sink thermistor open or malfunc-

55

tioning. Check thermistor/connections.

Undervolt Fault

Monitor the incoming AC line for low

04

voltage or line power interruption.

UV/UW/VW Short Fault Check motor and external wiring to
41, 42, 43

drive output terminals for a short.

Xsistr Desat Flt

One or more output transistors were

47

(Frame C & up only)

operating in active region, instead of
saturation. Check for damaged transis-
tors.

Drive Fault Reset

Power-up attempted with open Stop

22

contact or closed Start contact.

EE Init Read

Trouble reading EEPROM during

53

initialization. Check Power/Driver Bd.

EE Init Value

Stored parameter value out of range on

54

initialization. Check Power/Driver Bd.

EEprom Checksum

EEPROM checksum does not match.

66

Check connections to Power/Driver Bd.

EEprom Fault

EEPROM will not write a new value.

32

Check connections to Control Board.

FGND 10ms Over

Occurs if 10ms interrupt is pending

52

before current interrupt is complete.

Ground Fault

Check motor and external wiring to

13

drive output for a grounded condition.

Ground Warning

If enabled, indicates lower ground current

57

level than Ground Fault (see above).

Hertz Err Fault

No valid operating frequency. • Check

29

[Minimum/Maximum Freq] parameters
• Check [Skip Freq 1, 2, 3, Band] •
Check for loose connections or trans-
ducer loss at 4-20mA input, TB2.

Hertz Sel Fault

Reprogram [Freq Select 1] and/or

30

[Freq Select 2] with a correct value.

Loop Overrn Flt

Overrun of the 2.5ms control loop.

23

Check connections to the Driver Board.

Max Retries Fault

Check buffer for fault requiring reset.

33

Correct cause & clear by pressing local
Stop key or cycling TB3 Stop input.

Motor Mode Flt

Fault detected on Control Board. Check

24

connections to board/Language Module.

Motor Stall Fault

If motor is drawing excessive current

06

(over 150%), motor load is excessive
and will not allow the drive to acceler-
ate to set speed. A longer accel time or
a reduced load may be required.

Neg Slope Fault

Check programming. • [Maximum

35

Voltage] must be greater than [Base
Voltage]

1

• [Maximum Freq] must be

greater than [Base Frequency]

1

• [Base

Voltage] must be greater than [Start
Boost] • If [DC Boost Select] = “Full
Custom”, [Base Voltage] must be greater
than [Break Voltage] and [Break Voltage]
must be greater than [Start Boost].

Open Pot Fault

Check external pot. circuit at TB2 for an

09

open circuit.

Op Error Fault

• A SCANport™ device requests a read/

11

write of a data type not supported. •
[Motor Type] set to “Sync PM” & [Stop
Mode Used] set to “DC Brake” • [Motor
Type] set to “Sync Reluc” or “Sync PM”
& [Speed Control] set to “Slip Comp”.

Overcurrent Flt

Check for short circuit at drive output

12

or excessive load conditions at motor.

Publication 1336 PLUS-5.1 – May, 1997

Supersedes December, 1996

P/N 74001-004-01(K)

1

Firmware versions before 2.01 only.

2

Firmware versions 4.01 & up only.