Parameter list (continued), Programming system – Rockwell Automation 1336S ADJ FREQ AC DRIVE User Manual
Page 2
Programming System
Group/Param.
No.
Disp. Units
Min./Max. Values
Default
Owners
(continued)
Reference Owner
106
Bit 1/0
Read Only
None
Accel Owner
107
Bit 1/0
Read Only
None
Decel Owner
108
Bit 1/0
Read Only
None
Fault Owner
109
Bit 1/0
Read Only
None
MOP Owner
110
Bit 1/0
Read Only
None
Local Owner
179
Bit 1/0
Read Only
None
Adapter I/O
Data In (8)
111-118 Parameter #
None
0
Data Out (8)
119-126 Parameter #
None
0
Process Display
Process 1 Par
127
Parameter #
None
1
Process 1 Scale
128
0.01
±327.67
1.00
Process 1 Txt 1-8
129-136 ASCII Code
None
Volts
Process 2 Par
180
Parameter #
None
54
Process 2 Scale
181
0.01
±327.67
1.00
Process 2 Txt 1-8
182-189 ASCII Code
None
Amps
Encoder Feedback
Speed Control
77
Settings
Selection Parameter
Slip Comp
Encoder Type
152
Settings
Selection Parameter
Pulse
Pulse/Enc Scale
46
1 PPR
1/4096
1024 PPR
Maximum Speed
151
1 Hertz
0/400 Hz
400 Hz
Motor Poles
153
1 Pole
Read Only
None
Speed Ki
165
Numeric
0/20000
100
Speed Error
166
0.01 Hz
±8.33% [Base Frequency]
None
Speed Integral
167
0.01 Hz
±8.33% [Base Frequency]
None
Speed Adder
168
0.01 Hz
±8.33% [Base Frequency]
None
Motor NP RPM
177
1 RPM
60/24000 RPM
1750 RPM
Motor NP Hertz
178
1 Hertz
1/400 Hz
60 Hz
Pulse/Enc Hertz
2.01
63
0.01 Hertz
0.00/400.00 Hz
None
Process PI
3.01
Speed Control
77
Settings
Selection Parameter
Slip Comp
PI Config
213
Bit 1/0
0/1
00000000
PI Status
214
Bit 1/0
Read Only
None
PI Ref Select
215
Settings
Selection Parameter
Preset 1
PI Fdbk Select
216
Settings
Selection Parameter
0-10 Volt
PI Reference
217
0.01 Hertz
±400.00 Hz
None
PI Feedback
218
0.01 Hertz
±400.00 Hz
None
PI Error
219
0.01 Hertz
±400.00 Hz
None
PI Output
220
0.01 Hertz
±400.00 Hz
None
KI Process
221
N/A
0/1024
128
KP Process
222
N/A
0/1024
256
PI Neg Limit
223
0.01 Hz
±400.00 Hz
–8.33% [Max Freq]
PI Pos Limit
224
0.01 Hz
±400.00 Hz
+8.33% [Max Freq]
PI Preload
4.01
225
0.01 Hz
±8.33% [Max Freq]
0.00 Hz
Motor Control
4.01
Control Select
4.01
9
Settings
Selection Parameter
Sens Vector
Flux Amps Ref
4.01
192
0.1A
0.0/75% Drive VT Rtd. Amps 0.0A
IR Drop Volts
4.01
194
4.01
1 Volt
0/25% Drive Rated Volts
0 Volts
Flux Up Time
4.01
200
4.01
0.1 Sec
0.0/5.0 Sec
0.0 Sec
Start Boost
48
1 Volt
0/9.5% Drive Rated Volts
0 Volts
Run Boost
83
1 Volt
0/9.5% Drive Rated Volts
0 Volts
Boost Slope
4.01
169
None
1.0/8.0
1.5
Break Voltage
50
1 Volt
0/50% Drive Rated Volts
25% Max. Rtd. Vlt.
Break Frequency
49
1 Hertz
0/120 Hz
25% [Max. Freq]
Base Voltage
18
1 Volt
25/120% Drive Rated Volts
Drive Rtd. Volts
Base Frequency
17
1 Hertz
25/400 Hz
60 Hz
Maximum Voltage
20
1 Volt
25/120% Drive Rated Volts
Drive Rtd. Volts
Power-Up &
Status Display
Login,
Logout
Modify
Control Logic,
Fault Queue
"Choose Mode"
Process Display
or
or
or
or
Parameter Groups
(See Parameter List)
OPERATOR LEVEL
MODE LEVEL
GROUP LEVEL
PARAMETER LEVEL
Parameters
(See Parameter List)
Display
(Read Only)
Program
(Read/Write)
Password
EEPROM
Search
1
(Read Only)
Control
Status
1
Process
1
Series A (Version 3.0) and Series B HIM Only.
2
Series B HIM Only.
3
Reserved for Future Use.
Reset Defaults
Drive -> HIM
2
HIM -> Drive
2
Recall Values
3
Save Values
3
X.xx
Firmware version X.xx or later.
➀ These parameters are located in the “Diagnostics” group for firmware versions before 2.01.