Chapter 1
ATTENTION: - To reduce the risk of fire or electric shock, install this HC-DySC in
a temperature and humidity controlled, indoor environment, free of conductive
contaminants.
• Avoid installing the HC-DySC directly near heat-emitting equipment such as ovens, heaters, or
furnaces.
• Ambient temperature must not exceed 40°C (104°F).
• Do not operate near water or excessive humidity (95% max).
• When punching or drilling holes for conduit fittings, take care to avoid dropping metallic particles
inside the enclosure as this can result in electrical damage.
• The system is not intended for outdoor use.
• The operating environment should be maintained within the parameters stated in this manual.
• Only authorized service personnel should perform service on the HC-DySC.
• Ensure all power is disconnected before performing installation or service.
ATTENTION: Internal components can be easily damaged by electrostatic
discharge (ESD). Do not touch circuit boards or electronic components with
hands or metal objects. The HC-DySC is not rated to directly power life support
equipment.
• Ensure the area around the HC-DySC is clean and uncluttered.
• Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the
equipment.