Dielectric strength, Certifications – Rockwell Automation 1606-XLS960EE Power Supply Reference Manual User Manual
Page 18

All parameters are specified at 24V, 40A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
18
Rockwell Automation Publication 1606-RM029A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
21. Dielectric Strength
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the
voltage with a slow ramp (2s up and 2s down). Connect all input-terminals together as well as all output poles before
conducting the test. When testing, set the cut-off current settings to the value in the table below.
Fig. 21-1 Dielectric strength
A B C D
Type test
60s
2500Vac
3000Vac 500Vac 500Vac
Factory test
5s
2500Vac
2500Vac 500Vac 500Vac
Field test
5s
2000Vac
2000Vac
500Vac
500Vac
Cut-off current setting > 20mA
> 20mA
> 40mA
> 1mA
A
D
C
B
B
*)
L
Input
DC-ok
13
14
Earth, PE
Output
15/16
+/-
Shut-down
N
To fulfil the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the – pole or any other part of
the output circuit shall be connected to the protective earth
system. This helps to avoid situations in which a load starts
unexpectedly or can not be switched off when unnoticed earth
faults occur.
B*) When testing input to DC-OK ensure that the max. voltage between DC-OK and the output is not exceeded (column D). We recommend
connecting DC-OK pins and the output pins together when performing the test.
22. Certifications
EN 60950-1, EN 61204-3
- the CE EMC directive
- CE Low-Voltage Directives
UL 508
IND. CONT. EQ.
RECOGNIZED for use in the U.S.A. (UL 60950-1) and
Canada (C22.2 No. 60950)
Information Technology Equipment, Level 3
UL 60950-1
Marine
GL (Germanischer Lloyd) classified for marine and offshore
applications. Environmental Category: C, EMC2. See below
for link to the Certificate.
SEMI F47
SEMI F47-0706
Voltage Sag Immunity Compliance.
See below for link to the Certificate.
GOST R
GOST R certification is applicable for products intended for
sale and use within Russia. See below for link to Certificate.
Complies with
LISTED E56639 for use in the U.S.A, (UL 508) and Canada
(C22.2 No. 14.95)
Industrial Control Equipment
Marine RINA
RINA (Registro Italiano Navale) certified. See below for
link to the Certificate.
C-TICK
C-Tick compliance is for products for sale and use within
the Australian market. See below for link to the C-Tick
Declarations of Conformity.
Product certification information (including Certificates and Declarations of Conformity) can be found at
www.ab.com/certifications
.