Efficiency and power losses – Rockwell Automation 1606-XLS960EE Power Supply Reference Manual User Manual
Page 11
All parameters are specified at 24V, 40A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM029A-EN-P — April 2014
11
Bulletin 1606 Switched Mode Power Supplies
12. Efficiency and Power Losses
AC 230V
Efficiency
typ.
94.6%
at 24V, 40A
Average efficiency
*)
typ.
93.8%
25% at 10A, 25% at 20A, 25% at 30A. 25% at 40A
Power losses
typ.
3.2W
with activated shut-down
typ.
12.0W
at 24V, 0A (no load)
typ.
29.6W
at 24V, 20A (half load)
typ.
54.8W
at
24V,
40A
(full
load)
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
Fig. 12-1 Efficiency vs. output current at 24V,
typ.
Fig. 12-2 Losses vs. output current at 24V,
typ.
Efficiency
8
12
16
20
24
28
32
36 40A
91
92
93
Output Current
94
95%
Power Losses
0
4
8
12 16 20 24 28
40A
10
0
30
40
50
60W
32 36
20
Output Current
Fig. 12-3 Efficiency vs. input voltage at 24V,
40A, typ.
Fig. 12-4 Losses vs. input voltage at 24V, 40A,
typ.
Efficiency
170
190
210
230
250 270Vac
92
93
94
Input Voltage
95%
Power Losses
30
35
40
45
50
55
60W
170
190
210
230
250 270Vac
Input Voltage