All parameters are specified at 24V, 40A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM029A-EN-P — April 2014
17
Bulletin 1606 Switched Mode Power Supplies
19. Protection Features
Output protection
Electronically protected against overload, no-load and short-circuits
*)
Output over-voltage protection
typ. 30Vdc
max. 32Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protection
IP 20
EN/IEC 60529
Caution: For use in a controlled environment according
to CSA 22.2 No 107.1-01.
Penetration protection
> 5mm
e.g. screws, small parts
Over-temperature protection
yes
Output shut-down with automatic restart
Input transient protection
MOV (Metal Oxide Varistor)
Internal input fuse
included
not user replaceable
*) In case of a protection event, audible noise may occur.
20. Safety Features
Input / output separation
*)
SELV
IEC/EN
60950-1
PELV
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
double or reinforced insulation
Class of protection
I
PE (Protective Earth) connection required
Isolation resistance
> 5MOhm
input to output, 500Vdc
PE resistance
< 0.1Ohm
Touch current (leakage current)
typ. 0.59mA / 1.38mA
230Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.75mA / 1.74mA
264Vac, 50Hz, TN-,TT-mains / IT-mains
*) double or reinforced insulation