All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

4

Rockwell Automation Publication 1606-RM032A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

3. AC Input

AC input

nom.

3AC 380-480V

suitable for TN, TT and IT mains networks,
grounding of one phase is allowed except in UL 508
applications

AC input range

min.

3x 323-576Vac

continuous operation

Allowed voltage L to earth

max.

576Vac

continuous, IEC 60664-1

Input frequency

nom.

50–60Hz

±6%

Turn-on voltage

typ.

3x 305Vac

steady-state value, load independent, see Fig. 3-1

Shut-down voltage

typ.

3x 275Vac

steady-state value, load independent, see Fig. 3-1

3AC 400V

3AC 480V

Input current

typ.

1.65A

1.35A

at 48V, 20A, symmetrical phase voltages,
see Fig. 3-3

Power factor

*)

typ.

0.88

0.90

at 48V, 20A, see Fig. 3-4

Start-up delay

typ.

500ms

600ms

see Fig. 3-2

Rise time

typ.

23ms

23ms

at 48V, 20A, resistive load, 0mF see Fig. 3-2

typ.

47ms

47ms

at 48V, 20A, resistive load, 20mF see Fig. 3-2

Turn-on overshoot

max.

1V

1V

see Fig. 3-2

*)

The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.


Fig. 3-1 Input voltage range

Fig. 3-2 Turn-on behavior, definitions

Turn-on

323V

Rated input range

V

IN

P

OUT

275V

576Vac

Shut

-down

305V

Start-up

delay

Rise

Time

Overshoot

- 5%

Output
Voltage

Input
Voltage

L1 L2 L3

Fig. 3-3 Input current vs. output load at 48V

Fig. 3-4 Power factor vs. output load at 48V

20A

2

4

6

8 10 12 14 16 18

0

0.2

0.4

0.6

0.8

1.0

1.2

1.6A

Input Current, typ.

1.4

Output Current

A: 3x 400Vac

B: 3x 480Vac

A

B

Power Factor, typ.

2

4

6

8 10 12 14 16 18 20A

0.70

0.75

0.80

0.85

0.90

0.95

Output Current

A: 3x 400Vac

B: 3x 480Vac

A

B