All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
18
Rockwell Automation Publication 1606-RM032A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
21. Dielectric Strength
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the
voltage with a slow ramp (2s up and 2s down). Connect all phase terminals together as well as all output poles before
conducting the test. When testing, set the cut-off current settings to the value in the table below.
Fig. 21-1 Dielectric strength
A B C D
Type test
60s
2500Vac
3000Vac 500Vac 500Vac
Factory test
5s
2500Vac
2500Vac 500Vac 500Vac
Field test
5s
2000Vac
2000Vac
500Vac
500Vac
Cut-off current setting > 10mA
> 10mA
> 40mA
> 1mA
A
D
C
B
B
*)
L1
Input
Earth
L3
L2
DC-ok
13
14
Output
15/16
+/-
Shut-down
To fulfil the PELV requirements according to EN 60204-1 § 6.4.1, we
recommend that either the + pole, the – pole or any other part of
the output circuit shall be connected to the protective earth
system. This helps to avoid situations in which a load starts
unexpectedly or can not be switched off when unnoticed earth
faults occur.
B*) When testing input to DC-OK ensure that the max. voltage between DC-OK and the output is not exceeded (column D). We recommend
connecting DC-OK pins and the output pins together when performing the test.
22. Certifications
EN 60950-1, EN 61204-3
Complies with CE EMC and CE Low Voltage Directives
UL 508
IND. CONT. EQ.
LISTED E56639 for use in the U.S.A. (UL 508) and Canada
(C22.2 No. 14-95)
Industrial Control Equipment
UL 60950
RECOGNIZED E168663 for use in the U.S.A. (UL 60950-1) and
Canada (C22.2 No. 60950)
Information Technology Equipment, Level 3
Marine GL
GL (Germanischer Lloyd) classified for marine and offshore
applications. Environmental category: C, EMC2.
See below for link to the Certificate.
GOST R
Marine RINA
RINA (Registro Italiano Navale) certified. See below for link to
the Certificate.
GOST R certification is applicable for products intended for sale
and use within Russia. See below for link to the Certificate.
C-TICK
C-Tick compliance is for products intended for sale and use
within the Australian market. See below for the link to the
C-Tick Declarations of Conformity.
Product certification information (including Certificates and Declarations of Conformity) can be found at
www.ab.com/certifications
.