Mounting orientations – Rockwell Automation 1606-XLS960F-3 Power Supply Reference Manual User Manual
Page 27
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM032A-EN-P — April 2014
27
Bulletin 1606 Switched Mode Power Supplies
25.13. Mounting Orientations
Mounting orientations other than all terminals on the bottom require a reduction in continuous output power or a
limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime expectancy
of the power supply. Therefore, two different derating curves for continuous operation can be found below:
Curve A1
Recommended
output
current.
Curve A2
Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 25-10
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
INPUT
Output Current
0
10
20
30
40
60°C
5
10
15
20A
50
A1
Ambient Temperature
Fig. 25-11
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPUT
INPU
T
Output Current
0
10
20
30
40
60°C
5
10
15
20A
50
A2
Ambient Temperature
A1
Fig. 25-12
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10
20
30
40
60°C
5
10
15
20A
50
Ambient Temperature
A1
A2
Fig. 25-13
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTP
UT
IN
PUT
Output Current
0
10
20
30
40
60°C
5
10
15
20A
50
Ambient Temperature
A1
A2
Fig. 25-14
Mounting
Orientation E
(Horizontal ccw)
Power Supply
OUTPUT
INP
U
T
Output Current
0
10
20
30
40
60°C
5
10
15
20A
50
Ambient Temperature
A1
A2