Output – Rockwell Automation 1606-XLE480EPC Power Supply Reference Manual User Manual
Page 6

6
Rockwell Automation Publication 1606-RM001B-EN-P - August 2013
Bulletin 1606 Switched Mode Power Supplies
6. Output
Output voltage
nom.
24V
Adjustment range
min.
24-28V
guaranteed
max.
30V
****)
at clockwise end position of potentiometer
Factory settings
typ.
24.1V
±0.2%, at full load, cold unit, in “single use” mode
typ.
24.1V
±0.2%, at full load, cold unit, in “parallel use” mode
typ.
25.1V
at no load, cold unit, in “parallel use” mode
Line regulation
max.
10mV
85-300Vac
Load regulation
max.
100mV
in “single use” mode: static value, 0A
20A;
see
typ.
1000mV
in “parallel use” mode: static value, 0A
20A,
see
Ripple and noise voltage
max.
50mVpp
20Hz to 20MHz, 50Ohm
Output current
nom.
20A
at 24V, ambient temperature <60°C, see
nom.
24A
*)
at 24V, ambient temperature <45°C, see
nom.
17.1A
at 28V, ambient temperature <60°C, see
nom.
20.6A
*)
at 28V, ambient temperature <45°C, see
typ.
80A
up to 15ms, output voltage stays above 20V, see
available once every five seconds. Refer to
Peak Current Capability on page 19
for
more peak current measurements.
Output power
nom.
480W
continuously available
nom.
576W
*)
Power Boost
® *)
Overload behaviour
cont. current
output voltage > 13Vdc, see
Hiccup
PLUS
mode
**)
output voltage < 13Vdc, see
Short-circuit current
min.
35A
***)
load impedance <10mOhm, see
max.
45A
***)
load impedance <10mOhm, see
max.
15A
***)
average (R.M.S.) current, load impedance 50mOhm, see
min.
70A
up to 15ms, load impedance <10mOhm, see
typ.
100A
up to 15ms, load impedance <10mOhm, see
Output capacitance
typ.
7 000μF
included inside the power supply
*)
Power Boost This power/ current is continuously allowed up to an ambient temperature of 45°C. Above 45°C, do not use this power/ current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.
**) Hiccup
PLUS
Mode At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2s. After this, the output is switched off for approx. 18s before a new start attempt is automatically
performed. This cycle is repeated as long as the overload exists. If the overload has been cleared, the device will operate normally. See
***) Discharge current of output capacitors is not included.
****) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not guaranteed value which can be achieved. The typical value is about 28.5V (in “single use” mode).
Fig. 6-1: Output voltage vs. output current, typ.
Fig. 6-2: Output voltage in “parallel use” mode, typ.
Fig. 6-3: Short-circuit on output, Hiccup
PLUS
mode, typ.
Fig. 6-4: Dynamic overcurrent capability, typ.
Output Voltage (Single Use, typ.)
0
0
25
4
8
12
28V
16
20
24
40A
15
5
10
20
30
35
Adjustment
Range
Output Current
Continuous
current
Factory
setting
Hiccup
mode
Output Voltage (Parallel Use, typ.)
22V
0
8
16
23V
24V
25V
29V
26V
27V
28V
24A
20
12
4
Adjustment
Range
Factory
setting
Output Current