beautypg.com

2 back-feeding loads, 3 external input protection, 4 output circuit breakers – Rockwell Automation 1606-XLE480EPC Power Supply Reference Manual User Manual

Page 20: Back-feeding loads, External input protection, Output circuit breakers

background image

20

Rockwell Automation Publication 1606-RM001B-EN-P - August 2013

Bulletin 1606 Switched Mode Power Supplies

23.2

Back-feeding Loads

Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called return voltage immunity or
resistance against Back- E.M.F. (Electro Magnetic Force).

This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the
power supply is on or off.

The maximum allowed feed-back-voltage is 35V DC.

23.3 External Input Protection

The unit is tested and approved for branch circuits up to 30A (UL) and 32A (IEC). An external protection is only required if the supplying branch has an
ampacity greater than this. Check also local codes and local requirements. In some countries local regulations might apply.

If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker. A minimum
value of 10A B- or C-Characteristic breaker should be used.

23.4 Output Circuit Breakers

Standard miniature circuit breakers (MCB’s or UL 1077 circuit breakers) are commonly used for AC-supply systems and may also be used on 24V
branches.

MCB’s are designed to protect wires and circuits. If the ampere value and the characteristics of the MCB are adapted to the wire size that is used, the
wiring is considered as thermally safe regardless of whether the MCB opens or not.

To avoid voltage dips and under-voltage situations in adjacent 24V branches which are supplied by the same source, a fast (magnetic) tripping of the
MCB is desired. A quick shutdown within 10ms is necessary corresponding roughly to the ride-through time of PLC's. This requires power supplies with
high current reserves and large output capacitors. Furthermore, the impedance of the faulty branch must be sufficiently small in order for the current to
actually flow. The best current reserve in the power supply does not help if Ohm’s law does not permit current flow. The following table has typical test
results showing which B- and C-Characteristic MCBs magnetically trip depending on the wire cross section and wire length.

*)

Don’t forget to consider twice the distance to the load (or cable length) when calculating the total wire length (+ and – wire).

Fig.23-4 Test circuit

Maximal wire length

*)

for a fast (magnetic) tripping:

0.75mm²

1.0mm²

1.5mm²

2.5mm²

C-2A

29m

40m

56m

82m

C-3A

26m

35m

50m

77m

C-4A

21m

28m

36m

53m

C-6A

8m

10m

14m

25m

C-8A

4m

7m

11m

18m

C-10A

1m

2m

3m

6m

B-6A

17m

24m

35m

53m

B-10A

12m

16m

23m

32m

B-13A

9m

13m

20m

29m

B-16A

4m

7m

9m

17m

B-20A

1m

1m

2m

2m

MCB

Power Supply

AC

DC

+

-

+

-

Load

Wire length

S1... Fault simulation switch

S1

This manual is related to the following products: