16. Protection Features
*)
In case of a protection event, audible noise may occur.
17. Safety Features
18. Dielectric Strength
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer. Field tests may be
conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all input-
terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings to the value in the table below.
Output protection
Electronically protected against overload, no-load and short-circuits
*)
Output over-voltage protection
typ. 30.5Vdc
max. 32Vdc
In case of an internal power supply defect, a redundant circuit limits the maximum
output voltage. The output shuts down and automatically attempts to restart.
Degree of protection
IP 20
EN/IEC 60529
Penetration protection
> 5mm
e.g. screws, small parts
Over-temperature protection
yes
Output shut-down with automatic restart
Input transient protection
MOV (Metal Oxide Varistor)
Internal input fuse
included
not user replaceable
Input / output separation
*)
SELV
IEC/EN 60950-1
PELV
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
double or reinforced insulation
Class of protection
I
PE (Protective Earth) connection required
Isolation resistance
> 5MOhm
input to output, 500Vdc
PE resistance
< 0.1Ohm
Touch current (leakage current)
typ. 0.14mA / 0.37mA
100Vac, 50Hz, TN-,TT-mains / IT-mains
typ. 0.20mA / 0.55mA
120Vac, 60Hz, TN-,TT-mains / IT-mains
typ. 0.35mA / 0.87mA
230Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.17mA / 0.46mA
110Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.26mA / 0.67mA
132Vac, 60Hz, TN-,TT-mains / IT-mains
max. 0.46mA / 1.08mA
264Vac, 50Hz, TN-,TT-mains / IT-mains
*) double or reinforced insulation
Fig. 18-1:
Dielectric strength
A
B
C
D
Type test
60s
2500Vac
3000Vac
1500Vac
500Vac
Factory test
5s
2500Vac
2500Vac
1000Vac
500Vac
Field test
5s
2000Vac
2000Vac
1000Vac
500Vac
Cut-off current setting
> 15mA
> 15mA
> 20mA
> 1mA
To fulfil the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole,
the – pole or any other part of the output circuit shall be connected to the protective earth system. This
helps to avoid situations in which a load starts unexpectedly or can not be switched off when unnoticed
earth faults occur.
A
D
C
B
B
N
L
Input
DC-ok
Earth, PE
Output
-
+