14

Rockwell Automation Publication 1606-RM001B-EN-P - August 2013

Bulletin 1606 Switched Mode Power Supplies

16. Protection Features

*)

In case of a protection event, audible noise may occur.

17. Safety Features

18. Dielectric Strength

The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer. Field tests may be
conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all input-
terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings to the value in the table below.

Output protection

Electronically protected against overload, no-load and short-circuits

*)

Output over-voltage protection

typ. 30.5Vdc
max. 32Vdc

In case of an internal power supply defect, a redundant circuit limits the maximum
output voltage. The output shuts down and automatically attempts to restart.

Degree of protection

IP 20

EN/IEC 60529

Penetration protection

> 5mm

e.g. screws, small parts

Over-temperature protection

yes

Output shut-down with automatic restart

Input transient protection

MOV (Metal Oxide Varistor)

Internal input fuse

included

not user replaceable

Input / output separation

*)

SELV

IEC/EN 60950-1

PELV

IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41

double or reinforced insulation

Class of protection

I

PE (Protective Earth) connection required

Isolation resistance

> 5MOhm

input to output, 500Vdc

PE resistance

< 0.1Ohm

Touch current (leakage current)

typ. 0.14mA / 0.37mA

100Vac, 50Hz, TN-,TT-mains / IT-mains

typ. 0.20mA / 0.55mA

120Vac, 60Hz, TN-,TT-mains / IT-mains

typ. 0.35mA / 0.87mA

230Vac, 50Hz, TN-,TT-mains / IT-mains

max. 0.17mA / 0.46mA

110Vac, 50Hz, TN-,TT-mains / IT-mains

max. 0.26mA / 0.67mA

132Vac, 60Hz, TN-,TT-mains / IT-mains

max. 0.46mA / 1.08mA

264Vac, 50Hz, TN-,TT-mains / IT-mains

*) double or reinforced insulation

Fig. 18-1:

Dielectric strength

A

B

C

D

Type test

60s

2500Vac

3000Vac

1500Vac

500Vac

Factory test

5s

2500Vac

2500Vac

1000Vac

500Vac

Field test

5s

2000Vac

2000Vac

1000Vac

500Vac

Cut-off current setting

> 15mA

> 15mA

> 20mA

> 1mA

To fulfil the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole,
the – pole or any other part of the output circuit shall be connected to the protective earth system. This
helps to avoid situations in which a load starts unexpectedly or can not be switched off when unnoticed
earth faults occur.

A

D

C

B

B

N

L

Input

DC-ok

Earth, PE

Output

-

+