Output in normal mode – Rockwell Automation 1606-XLS240-UPS Power Supply Reference Manual User Manual
Page 5
All parameters are specified at 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM036A-EN-P — April 2014
5
Bulletin 1606 Switched Mode Power Supplies
6. Output in Normal Mode
nom.
DC 24V
The output voltage follows the input voltage reduced by
the input to output voltage drop.
Output voltage in normal mode
max.
0.3V
At 10A output current, see Fig. 6-1 for typical values
Voltage drop between input and
output
max.
0.45V
At 15A output current, see Fig. 6-1 for typical values
Ripple and noise voltage
max.
20mVpp
20Hz to 20MHz, 50Ohm *)
Output current
nom.
15A
Continuously allowed
Output power
nom.
360W
Continuously allowed
Short-circuit current
min.
17.9A
Load impedance 100mOhm, see Fig. 6-2 for typical values
max.
21A
Load impedance 100mOhm, see Fig. 6-2 for typical values
Capacitive and inductive loads
No limitation
*) This figure shows the ripple and noise voltage which is generated by the DC-UPS. The ripple and noise voltage
might be higher if the supplying source has a higher ripple and noise voltage.
Fig. 6-2 Output voltage vs. output current in
normal mode at 24V input, typ.
Fig. 6-1 Input to output voltage drop, typ.
Input to Output
Voltage drop
0
0
2
10
0.1
0.15
0.25
18A
0.05
0.2
0.3
0.35
0.4V
Ou t pu t Cu r r e n t
4
6
8
12 14 16
Output Voltage
0
0
5
10
15
20
4
8
12
28V
16
20
24
25A
Output Current