Rockwell Automation 1606-XLS240-UPS Power Supply Reference Manual User Manual
Page 16

All parameters are specified at 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
16
Rockwell Automation Publication 1606-RM036A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
17. EMC
The unit is suitable for applications in industrial environments as well as in residential, commercial amnd light industry
environments without any restrictions. The CE Mark is in conformance with EMC guidelines 89/336/EEC and 93/68/EEC
and the low-voltage directive (LVD) 73/23/EEC, 93/68/EEC.
A detailed EMC report is available on request.
EMC Immunity
EN 61000-6-1, EN 61000-6-2
Generic standards
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
8kV
15kV
Criterion A*)
Criterion A *)
Electromagnetic RF field
EN 61000-4-3
80MHz-1GHz 10V/m Criterion
A
Fast transients (Burst)
EN 61000-4-4
Out- and input lines
2kV
Criterion A
Signal lines **)
2kV
Criterion A
Surge voltage
EN 61000-4-5
Output + -
Input + -
+ / - housing
500V
500V
500V
Criterion A
Criterion A
Criterion A
Conducted disturbance
EN 61000-4-6 0,15-80MHz
10V
Criterion
A
*)
Grounded to the DIN rail
**) Tested
with
coupling
clamp
EMC Emission
EN 61000-6-3, EN 61000-6-4
Generic standards
Conducted emission
EN 55022
Input lines
Class B *)
EN 55022
Output lines
Class B *)
Radiated emission
EN 55011, EN 55022
Class B
This device complies with FCC Part 15 rules.
Operation is subjected to the following two conditions: (1) this device may not cause harmful interference, and 2) this
device must accept any interference received, including interference that may cause undesired operation.
*)
Informative measurement with voltage probe
Switching frequencies
The DC-UPS has three converters with three different
switching frequencies included.
Switching frequency of boost converter
100kHz
Constant frequency
Switching frequency of electronic output cu rrent limitation
78kHz
Constant frequency
Switching frequency of battery charger
19.5kHz
Constant frequency