All parameters are specified at 124V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
22
Rockwell Automation Publication 1606-RM006A-EN-P - January 2014
Bulletin 1606 Switched Mode Power Supplies
20.11.Mounting Orientations
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1
Recommended output current.
Curve A2
Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 20-5
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
INPUT
Output Power
0
10
20
30
40
60°C
6
18
24
30W
50
A1
12
Ambient Temperature
Fig. 20-6
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPU
T
INPUT
Output Power
0
10
20
30
40
60°C
6
18
24
30W
50
12
A1
A2
Ambient Temperature
Fig. 20-7
Mounting
Orientation C
(Table-top
mounting)
Output Power
0
10
20
30
40
60°C
6
18
24
30W
50
12
A1
A2
Ambient Temperature
Fig. 20-8
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
INPUT
Output Power
0
10
20
30
40
60°C
6
18
24
30W
50
12
A1
A2
Ambient Temperature
Fig. 20-9
Mounting
Orientation E
(Horizontal ccw)
Power Supply
OUTPUT
IN
PUT
Output Power
0
10
20
30
40
60°C
6
18
24
30W
50
12
A1
A2
Ambient Temperature