20.8. Operation on Two Phases
The power supply can also be used on two-phases of a three-phase-system. A
phase-to-phase connection is allowed as long as the supplying voltage is
below 240V
+10%
. Use a fuse or a circuit breaker to protect the N input. The N
input is not internally protected and is in this case connected to a hot wire.
Appropriate fuses or circuit breakers are specified in section 20.4.
20.9. Use without PE on the Input
From a safety standpoint, the unit is internally designed according to the requirements for Protection Class 1 and 2.
Please contact R-A if you decide not to use the PE terminal. A different marking of the front foil will then required.
Grounding of the input is beneficial for a high EMI immunity: symmetrical spikes or fast transients on the input side
can be conducted directly to earth by the built-in filter capacitors. The magnitude of such spikes or fast transients on
the output side caused by the input is much smaller compared to not connecting this terminal to ground.
Fig. 20-3 Grounded input
Fig. 20-4 Ungrounded input