beautypg.com

Connecting rod adjustment procedure – Rockwell Automation 1494V-DSxx Series D Variable Depth Disconnect Switch User Manual

Page 4

background image

(4)

Connecting Rod Adjustment Procedure

"ON" Position

Move disconnect handle to the "ON" position.
If switch does not fully close, return handle to "OFF" position.
Remove link spring hitch pin and disengage the connectiong rod from the primary link.
Turn connecting rod counter-clockwise (1 or more) full turns.
Re-engage connecting rod in primary link of handle, insert hitch pin and re-test
Repeat

-

as necessary.

Re-install link spring

"OFF" Position

Move disconnect handle to the "OFF" position.
If switch does not fully open, return handle to "ON" position.
Remove hitch pin and link spring, then disengage the connectiong rod from the primary link.
Turn connecting rod clockwise (1 or more) full turns.
Re-engage connecting rod in primary link of handle, insert hitch pin and re-test.
Repeat

-

as necessary.

Re-install link spring

1

2

Connecting

Rod

Hitch Pin

Primary Link

Drive Bar

PN-47400
DIR 10000056505 (Version 00)