Ac-input – Rockwell Automation 1606-XLP60EQ Power Supply Reference Manual User Manual
Page 4
![background image](/manuals/578210/4/background.png)
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
4
Rockwell Automation Publication 1606-RM007A-EN-P - February 2014
Bulletin 1606 Switched Mode Power Supplies
3. AC-Input
AC input
nom.
AC 100-240V
-15% / +10%, TN/TT/IT-mains
AC input range
85-264Vac
continuous operation, reduce output power linearly
to 50W between 90Vac and 85Vac at ambient
temperatures above +45°C, see Fig. 3-5
264–300Vac
<
0.5s
Allowed voltage L or N to earth
max.
264Vac or 375Vdc
Input frequency
nom.
50–60Hz
±6%
Turn-on voltage
typ.
65Vac
Shut-down voltage
typ.
see Fig. 3-1
AC 100V
AC 120V
AC 230V
Input current (rms)
typ.
1.14A
0.98A
0.58A
at 24V, 2.5A see Fig. 3-3
Power factor *)
typ.
0.61
0.58
0.50
at 24V, 2.5A see Fig. 3-4
Crest factor **)
typ.
3.2
3.3
3.7
at 24V, 2.5A
Start-up delay
typ.
170ms ***)
110ms ***)
90ms
see Fig. 3-2
Rise time
typ.
50ms
50ms
60ms
at 24V, 2.5A, 0mF, see Fig. 3-2
120ms
110ms
140ms
at
24V,
2.5A,
2.5mF
Turn-on
overshoot
max.
200mV 200mV 200mV
see
Fig.
3-2
*)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
***) At low temperatures, start-up attempts may occur which extends the start-up delay.
Fig. 3-1
Input voltage range
Fig. 3-2
Turn-on behavior, definitions
85
Rated
input range
max.
500ms
V
IN
V
OUT
300Vac
264
65
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3
Input current vs. output load at 24V
Fig. 3-4
Power factor vs. output load at 24V
2.5A
0.5
1.5
0
0
0.4
1.2A
Input Current, typ.
2.0
0.8
1.0
1.0
0.6
0.2
b
c
a
a) 100Vac
b) 120Vac
c) 230Vac
Output Current
2.5A
0
0.5
1.0
2.0
0.40
0.45
0.50
0.55
0.60
0.65
Power Factor, typ.
a) 100Vac
b) 120Vac
c) 230Vac
b
c
a
1.5
Output Current