All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

22

Rockwell Automation Publication 1606-RM007A-EN-P - February 2014

Bulletin 1606 Switched Mode Power Supplies

22.12. Use in a Tightly-Sealed Enclosure

When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher
than outside. In such situations, the inside temperature defines the ambient temperature for the power supply.

The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.

The power supply is placed in the middle of the box; no other heat producing item is inside the box.

Enclosure:

Rittal Type IP66 Box PK 9510 100, plastic, 130x130x75mm

Input:

230Vac

Case A:
Load:

24V,

2.5A;

load

is

placed

outside

the

box

Temperature inside the box:

40.1°C (in the middle of the right side of the power supply with a distance of 1cm)

Temperature outside the box:

21.9°C

Temperature rise:

18.2K

Case B:
Load:

24V, 2.0A; (=80%) load is placed outside the box

Temperature inside the box:

38.4°C (in the middle of the right side of the power supply with a distance of 1cm)

Temperature outside the box:

22.0°C

Temperature rise:

16.4K