beautypg.com

Rockwell Automation 160 SSC Series C FRN 7.xx User Manual

Page 54

background image

5-16

Parameters and Programming

PI Control Block Diagram

Figure 5.1

81

[PI Proportional Gain]

Proportional gain used by the PI regulator. This parameter is scaled so that when
it is set to 1.0, the process response is 1 Hz when the process error is 1%. The
correct value for this parameter depends on the dynamics of the process being
controlled, as well as the desired response. This parameter is active when
P46 - [Input Mode] setting 9 is used.

0/10.00

Numeric
Value

0.01

82

[PI Integral Gain]

Integral Gain used by the PI regulator. This parameter is scaled so that when it
is set to 1.0, the process response is 10 Hz/sec when the process error is 1%.
The correct value for this parameter depends on the dynamics of the process
being controlled, as well as the desired response. This parameter is active when
P46 - [Input Mode] setting 9 is used.

0/10.00

Numeric
Value

0.01

83

[PI Process Reference]

The PI control will regulate to this set point value. It represents a percentage of
the analog input. This parameter is active when P46 - [Input Mode] setting 9 is
used. This parameter along with P72 - [Slip Compensation] also activates PI
control in drives using Firmware Version FRN 7.06. See page 5-17 for PI Control
Setup and Activation instructions.

0/100.0%

0.1%

0.0%

84

[PI Dead Band]

The PI control will ignore errors less than this value. This parameter is active when
P46 - [Input Mode] setting 9 is used.

0/10.0%

0.1%

0.0%

Program Group

No.

Parameter Name/Description

Min./Max.
Range

Units

Factory
Default

ATTENTION: Hazard of personal injury or equipment damage

exists due to unpredictable changes in motor speed. Do not use

P72 - [Slip Compensation] and P83 - [Process Reference] to disable

PI control while the drive is running. Disable PI control only when
the drive is stopped.

This parameter applies only to the Analog Signal Follower model.

P83 -
[PI Process
Reference]

P81 -
[PI Proportional
Gain]

P84 -
[PI Dead Band]

P01 -
[Output
Frequency]

P82 -
[PI Integral
Gain]

Analog
Feedback

P58 -
[Internal
Frequency]

+

-

+

+

TB3-8 Open

TB3-8 Closed