beautypg.com

Ventilated enclosures, Non-ventilated enclosures – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 29

background image

Installation

2-3

Ventilated Enclosures

For Type 1 (IP42) enclosures, the following guidelines are
recommended to limit the maximum controller ambient temperature.

There should be a clearance of at least six inches (15 cm) above and
below the controller. This area allows air to flow through the
heatsink. Ventilation openings are required above and below this air
space.

The ventilation outlet should be placed at least six inches (15 cm)
above the controller with the ventilation inlet placed near the bottom
of the enclosure. A filter is required to prevent contaminants from
entering the enclosure.

Use the table below to determine the minimum ventilation openings
and fan/blower requirements.

Table 2.B Minimum Ventilation Openings

Cutout size assumes 50% blockage (filters, louvers, etc.)

Cutout size is the same as required for the particular fan or blower being used.

Dimensions are in centimeters (inches in parentheses).

Non-ventilated Enclosures

For Type 12 (IP54) or non-ventilated enclosures, it is recommended
that a bypass contactor be used. This will allow the SMC Dialog Plus
controller to bring the motor up-to-speed. After the controller is up to
full voltage, it is bypassed. Note that the Energy Saver, Phase
Rebalance, some metering functions, and some protective features of
the controller may no longer be available. See Figure 3.17 on page 3-
13 for this configuration.

SMC Rating

Top Cutout

①③

Bottom Cutout

①③

Fan Size

24–54A

65 cm

2

(10 in

2

)

65 cm

2

(10 in

2

)

110 CFM

97 and 135A

233 cm

2

(36 in

2

)

233 cm

2

(36 in

2

)

110 CFM

180A

13 Ч 51
(5 Ч 20)

100 CFM

240A

13 Ч 51
(5 Ч 20)

250 CFM

360A

13 Ч 51
(5 Ч 20)

(2) 250 CFM

500A

13 Ч 41
(5 Ч 16)

275 CFM

650A

13 Ч 76
(5 Ч 30)

(3) 240 CFM

720A

13 Ч 76
(5 Ч 30)

(3) 240 CFM

850A

13 Ч 76
(5 Ч 30)

(3) 240 CFM

1000A

13 Ч 76
(5 Ч 30)

(3) 240 CFM