Jumper installation, removal and storage, Drive identification – Rockwell Automation 20G PowerFlex 750-Series Power Jumpers User Manual
Page 4

4
Rockwell Automation Publication 750-IN011E-EN-P - February 2014
PowerFlex 750-Series Power Jumpers
Jumper Installation,
Removal and Storage
Jumper screws (Frames 2…5),
wires (Frames 1, 6 & 7) or plugs
(Frames 8…10) are used to
complete an electrical
connection when installed/
connected. When power jumper
screws are not used, they are
stored on the left interior chassis
wall as shown.
When installing a jumper screw or wire, note the recommended torque listed.
Drive Identification
The “Voltage Code” and “Default
Power Jumper Configuration” are
on the drive nameplate. Use this
information to perform the
proper procedure in the following
tables.
ATTENTION: Hazard of equipment damage exists if jumpers are not properly
disconnected.
For Frames 2…5, completely remove the jumper screw from the circuit board.
Frames 1, 6 & 7, secure the disconnected jumper wire to the standoff provided.
Frames 8…10 drive assemblies, secure the disconnected jumper plug in the socket
provided and ensure that all drive assemblies are identically configured.
Frames
Recommended Torque
Recommended Screwdriver/Socket
1
Not Applicable
Not Applicable
2…5
1.36 N•m (12.0 lb•in)
±0.14 N•m (1.2 lb•in)
6.4 mm (0.25 in.) flat or T15 Hexalobular
6…7
1.36 N•m (12.0 lb•in)
7 mm socket or T20 Hexalobular
Drive Power Jumpers
Frame 4 Shown
Jumper Screws
Installed
Jumper Screws Not
Installed
Jumper Screw Storage
Cat No. 20G11 N
D
011
A
A0NNNNN
UL Type 1 - only with Debris Hood and Conduit Plate
UL Open Type/IP20 - without Debris Hood and Conduit Plate
Specifications and Custom Catalog Number
representing options installed at factory.
See Nameplate 2 (Located behind HIM)
for equivalent base catalog number and separate options
Nameplate 1:
Mfd. in 2009 on Jan. 19
Series: A
Input: 3 Phase, 47-63Hz
AC Voltage Range
Amps ND (HD)
Power ND (HD)
Output: 3 Phase, 0-400 Hz
AC Voltage Range
Base Frequency (default)
Continuous Amps ND (HD)
60Sec Ovld Amps ND (HD)
3 Sec Ovld Amps ND (HD)
0-400
50 Hz
342-440
432-528
0-460
60 Hz
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
5.5 HP (4 HP)
7.5 HP (5 HP)
N223
Serial Number: xxxxxxxx
Original Firmware: x.xxx
TUV
Rheinland
Product Safety
.
.
Production inspected
W
E
C
EN 61800-5-1
Made in the U.S.A. Fac1C
400V Class
480V Class
II (2) G D
Functional Safety
Type approved
Voltage Code
Default Power Jumper Configuration