Operating instructions
M 8200
GB
6
Technical Data
min.
typ.
max.
General
Protection class
I
Housing protection
IP 65 (control cabinet, standard rail)
Supply voltage U
V
19.2 V
24 V
28.8 V
Residual ripple
1
)
5 V
SS
Power concumption (no load)
0.3 A (6 W)
Inputs Command unit
Start key
T 13, T 14
NO contact
Command unit actuation time period
30 ms
Contactor monitoring
T 21, T 22 contactor monitoring
NC contacts in series
Permissible contactor drop-off time
No restrictions
Permissible contactor response time
200 ms
Sensor signal T 3, T 4
Two-channel
Input resistance (active)
606
Ω
674
Ω
742
Ω
Signal active at
17.6 V
U
V
Signal LOW at
0 V
2.4 V
Time period tolerance between T 3 and T 4
15 ms
Outputs
Response time
15 ms
2
)
Switching current
< 0.1 mA
3
)
4 A
Switching voltage AC / DC
240 V AC /
60 V DC
Switching AC / DC
1200 VA /
50 W
Mech. life expectancy (switch actions)
10
7
Elec. life expectancy (switch actions)
10
9
Delay on Energisation (NO contacts)
40 ms
Delay on Energisation (NC contacts)
15 ms
Supply voltage
U
V
Connection
Pluggable strip terminal
Cable cross section
2.5 mm
2
Load capacity of terminals
(C 1 ... 4, D 1 ... 4)
2.5 A
Operating data
Safety category
Type 4
Tested to
pr EN 50 100 Part 1 and 2
Ambient operating temperature
0 °C
+55 °C
Storage temperature
–25 °C
+ 75 °C
Relative humidity (non condensing)
15 %
95 %
Vibration specification
5 g, 10 ... 55 Hz as per IEC 68-2-29
Shock resistance
10 g, 16 ms as per IEC 68-2-29
Dimensions (W x H x D)
152 x 73 x 118 mm
3
Electrical Connections
Chapter 6