Rockwell Automation 150 SMC Flex Quick Start User Manual
Page 12
12
SMC™ Flex Quick Start
Access the Basic set up group by selecting the Parameters menu from the Main Menu and then Set Up.This
programming group provides a limited parameter set, allowing quick start-up with minimal adjustment.
Parameter Name and Description
Values
Default
Parameter # 14 - SMC Option
Displays the type of controller. This is factory set and not adjustable.
Standard, Pump Control, Brake
Read Only
Parameter # 15 - Motor Connection
Displays the motor type to which the device is being connected.
Line or Delta
Line
Parameter # 16 - Line Voltage
Displays the system line voltage to which the unit is connected.
0…10000
480
Parameter # 17 - Starting Mode
Allows the user to program the SMC-Flex controller for the type of starting that best fits the application.
Soft Start, Current Limit, Full
Voltage, Linear Speed, Pump
Control
Soft Start
Parameter # 18 - Ramp Time
This sets the time period during which the controller will ramp the output voltage.
0…30 s
10
Parameter # 19 - Initial Torque
When the Soft Start mode is selected, this parameter sets the initial reduced voltage output level for the
voltage ramp.
0…90% of locked rotor torque
70
Parameter # 20 - Current Limit Level
When Current Limit mode is selected, this parameters sets level of current that is applied for the
programmed Ramp Time.
50…600% FLC
350
Parameter # 22 - Kickstart Time
A boost current is provided to the motor for the programmed time period.
0.0…2.0 s
0
Parameter # 23 - Kickstart Level
Adjusts the amount of current applied to the motor during kickstart.
0…90% of locked rotor torque
0
Parameter # 133 - Stop Input
Allows the user to select the operation of terminal 18, Stop Input.
Coast, Stop Option
Coast
Parameter # 132 - Option Input 1
Allows the user to select the operation of terminal 16, Option Input #1.
Disable, Coast, Stop Option,
Fault, Fault NC, Network
Stop Option
Parameter # 24 - Option Input 2
Allows the user to select the operation of terminal 15, Option Input #2.
Disable, Slow Speed, Dual Ramp,
Fault, Fault NC, Network, Clear
Fault
Disable
Parameter # 32 - Stop Mode
Allows the user to program the SMC Flex controller for the type of stopping that best fits the application.
Soft Stop, Linear Speed, SMB,
Accu-Stop, Pump Stop
Soft Stop
Parameter # 33 - Stop Time
This sets the time period which the controller will ramp the voltage during a stopping maneuver.
0.0…120 s
0.0
Parameter # 44 - Overload Class
Allows the user to enter the desired Overload trip class for the motor.
Disable, 10, 15, 20, 30
10
Parameter # 45 - Service Factor
Allows the user to enter the Service Factor of the motor. For IEC motors the typical value is 1.0. For NEMA
0.01…1.99
1.15
Parameter # 46 - Motor FLC
This is a user entered value that is needed so the device can provide proper motor Overload protection.
1.0…2200
1.0
Parameter # 47 - OL Reset Mode
This value allows the user to define how the overload can reset.
Auto, Manual
Manual
Parameter # 107 - Aux1 Config
Auxiliary 1 contact is located at terminals 19 and 20 and allows the user to configure the operation of the
contact.
Normal, Up-to-speed, Fault,
Alarm, Network Control, External
Bypass: (N.O./N.C.)
Normal
Parameter # 110 - Aux2 Config
Auxiliary 2 contact is located at terminals 29 and 30 and allows the user to configure the operation of the
contact.
Normal, Up-to-speed, Fault,
Alarm, Network Control, External
Bypass: (N.O./N.C.)
Fault
Parameter # 108 - Aux3 Config
Auxiliary 3 contact is located at terminals 31 and 32 and allows the user to configure the operation of the
contact.
Normal, Up-to-speed, Fault,
Alarm, Network Control, External
Bypass: (N.O./N.C.)
Alarm
Parameter # 109 - Aux4 Config
Auxiliary 4 contact is located at terminals 33 and 34 and allows the user to configure the operation of the
contact.
Normal, Up-to-speed, Fault,
Alarm, Network Control, External
Bypass: (N.O./N.C.)
Normal
Parameter # 115 - Parameter Mgmt
Allows the user the ability to recall all Factory default parameter values.
Ready, Load Default
Ready