Chapter 3

Verify Operation

Functional Proof Testing for Systems with Thermostat Contacts

Build a test fixture with a switch, a spare terminal plug (see

Catalog Numbers for

Spare Terminal Plugs on page 5

), and this schematic.

Follow these steps to perform the thermostat contacts functional proof test.

1. Close SW1.
2. Run the drive.
3. Open SW1.

If the system is working correctly, the drive faults due to a motor
over-temperature event detection. See

ATEX Fault Descriptions on

page 34

.

4. If a safety option is present, check parameter 933 [Start Inhibits] and

verify that bit 2 [Enabled] and bit 7 [Safety] are set to high.

Motors with Positive
Temperature Coefficient
(PTC) Devices

PTC-type devices are arranged in series throughout the motor. The resistance of
each PTC goes up as the motor temperature rises. The ATEX option module
with 11-Series I/O option module can detect an over-temperature event. See

General Specifications on page 37

for PTC trip resistance thresholds.

SW1