Rockwell Automation 20-750-ATEX PowerFlex 750-Series ATEX Option Module User Manual

Page 20

background image

20

Rockwell Automation Publication 750-UM003B-EN-P - July 2013

Chapter 2

Installation and Wiring

ATEX Option Module and 11-Series I/O Option Module with a Safety
Option Module

Follow these steps to configure the ATEX option module with 11-Series I/O
option module for use with a safe torque-off (catalog number 20-750-S) or safe
speed monitor (catalog number 20-750-S1) option module.

1. Set switch S1-1 to OFF.
2. Set switch S1-2 for Thermostat mode or PTC mode.

3. Remove the safety enable jumper on the main control board.

Configuration of the safety enable jumper on the main control board is a
requirement of each safety option module. For more information on these
requirements, refer to the specific option module user manual:

PowerFlex 750-Series Safe Torque Off User Manual,

publication

750-UM002

Safe Speed Monitor Option Module for PowerFlex 750-Series AC Drives

Safety Reference Manual, publication

750-RM001

Switch

Setting

Description

S1-1

OFF

Configures the ATEX option module for use with an additional safety
option module.

S1-2

OFF

Configures the ATEX option module for Thermostat mode,
over-temperature monitoring.
Can be used with PTC-type thermal sensors if short-circuit monitoring is
not needed.

ON

Configures the ATEX option module for PTC mode.
Provides both over-temperature and short-circuit monitoring.

S1-1

S1-2

S1-2

PowerFlex 753

PowerFlex 755

IMPORTANT

The default setting of the safety
enable jumper = installed.

For this step, verify that the safety
enable jumper is removed.