Environmental specifications – Rockwell Automation 21G PowerFlex 750 Series Safe Torque Off User Manual
Page 34
34
Rockwell Automation Publication 750-UM002F-EN-P - July 2013
Appendix A
Specifications
Environmental Specifications
Category
Specification
Maximum Surrounding Air Temperature
IP20, NEMA/UL Open Type:
IP00, NEMA/UL Open Type:
IP20, NEMA/UL Type 1 (w/Hood):
IP20, NEMA/UL Type 1 (w/Label):
IP20, NEMA/UL Type 1 (MCC Cabinet):
Flange Mount –
Front:
IP20, NEMA/UL Open Type:
IP00, NEMA/UL Open Type:
Back/Heat Sink:
IP66, NEMA/UL Type 4X
Stand-alone/Wall Mount –
IP54, NEMA/UL Type 12
0…50 °C (32…122 °F)
0…50 °C (32…122 °F)
0…40 °C (32…104 °F)
0…40 °C (32…104 °F)
0…40 °C (32…104 °F)
0…50 °C (32…122 °F)
0…50 °C (32…122 °F)
0…40 °C (32…104 °F)
0…40 °C (32…104 °F)
Frame 1…5, All Ratings
Frame 6…7, All Ratings
Frame 1…5, All Ratings
Frame 6…7, All Ratings
Frame 8…10, All Ratings
Frame 2…5, All Ratings
Frame 6…7, All Ratings
Frame 2…7, All Ratings
Frame 2…7, All Ratings
Storage Temperature (all const.):
-40…70 °C (-40…158 °F)
Atmosphere:
Important: Drive must not be installed in an area where the ambient
atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is
not going to be installed for a period of time, it must be stored in an area
where it will not be exposed to a corrosive atmosphere.
Important: Drives used with the safety function shall be protected against
contaminants to an IP54 level. This can be accomplished by using IP54 rated
enclosure or providing a dust free environment.
UV Radiation
The HIM and IP54, NEMA/UL Type 12 drive plastics are not UV rated.
Relative Humidity:
5…95% non-condensing
Shock - Operating
Shock - Packaged for Shipment
Frame 1…6:
Frame 7:
Frame 8…10:
Frame 1…2:
Frame 3…4:
Frame 5:
Frame 6…10:
15 g peak for 11 ms duration (±1.0 ms)
10 g peak for 11 ms duration (±1.0 ms)
Power Core - 10 g peak for 11 ms duration
(±1.0 ms) in Cabinet w/Option Bay - 5 g peak
for 11 ms duration (±1.0 ms)
381 mm (15 in.) drop height
330 mm (13 in.) drop height
305 mm (12 in.) drop height
Meets International Safe Transit Association
(ISTA) test procedure 2B
Vibration - Operating
Vibration - Packaged for Shipment
Sinusoidal Loose Load:
Random Secured:
Frame 1…2:
Frame 3…5:
Frame 6…7:
Frame 8…10:
Frame 1…5:
Frame 6…10:
Frame 1…5:
Frame 6…10:
1.000 mm (0.040 in.) displacement, 2 g peak
1.000 mm (0.040 in.) displacement, 1.5 g peak
1.000 mm (0.040 in.) displacement, 1 g peak
Power Core, Drive in Cabinet w/Option Bay -
1.000 mm (0.040 in.) displacement, 1 g peak
20.0 mm (0.8 in.) peak to peak, 2…5.186 Hz;
1.1 g peak from 5.186…20 Hz
Meets ISTA 2B packaging standards
Frequency (Hz)
PSD (g
2
/Hz)
1
0.00005
4
0.01
16
0.01
40
0.001
80
0.001
200
0.00001
Meets International Safe Transit Association
(ISTA) test procedure 2B