beautypg.com

Rockwell Automation 193/592-EC1/EC3/EC5 E3 and E3 Plus Solid-State Overload Relay - Quick Reference User Manual

Page 31

background image

31

Publication 193-QR003B-EN-P - October 2009

Table 13: High Fault Short-Circuit Ratings per UL 508 and CSA 22.2, No. 14 with
NEMA contactors

Cat. No.

Contactor
Size

Max. Available
Fault Current
[A]

Max.
Voltage
[V]

Max. UL Fuse [A]

Circuit Breaker/
Limiter

R

J

592-EC1
592-EC2
592-EC3
592-EC5

_T

00

100000

600

20

_C

0

100000

240

30

30

FDB 3025/

LFB3070R

480

30

30

FDB 3025/

LFB3070R

600

30

30

_C

1

100000

240

60

100

FDB 3050/

LFB3035R

480

30

50

FDB 3050/

LFB3035R

600

30

50

_C

2

100000

240

100

200

FDB 3100/

LFB3150R

480

60

100

600

60

100

_D

3

100000

240

200

350

FDB 3150/

LFB3150R

480

100

200

FDB 3125/

LFB3150R

600

100

200

FDB 3100/

LFB3150R

Table 14: IFC Short-Circuit Ratings per EN60947-4-1

Cat. No.

Prospective
Short-Circuit
Current I

r

[A]

Conditional
Short-Circuit
Current I

q

[A]

Max. Voltage [V]

193-EC_B, 592EC_T

1000

100000

690

193-EC_D, 592EC_C

3000

193-EC_E, 592EC_D

5000

193-EC_F

10000

193-EC_G

18000

193-EC_H

30000

193-EC_Z

1000