Rockwell Automation 193/592-EC1/EC3/EC5 E3 and E3 Plus Solid-State Overload Relay - Quick Reference User Manual
Page 20

20
Publication 193-QR003B-EN-P - October 2009
➊ The inhibit time setting parameters are applicable to both the trip and warning functions.
➋ FLA Setting range and default values are dependent upon the current rating of the product. See the user
manual for more information.
➌
Phase loss trip level is factory-set at a current imbalance greater than or equal to 100% and is not
user-adjustable.
➍ Must use Ground Fault Sensors (Cat. No. 193-CBCT_).
➎
Stall protection is only applicable during the motor starting sequence. If any phase of current falls below the
programmed Stall Trip Level, stall protection is disabled.
➏ 50…100% for devices with FRN 1.003 and earlier.
➐ Available on 193/592-EC5 only.
Under
Consumed
kVAR ➐
Disabled
0…32767
0.1…25.0 s
1.0 s
0…250 s
10 s
Over Consumed
kVAR ➐
Disabled
0…32767
0.1…25.0 s
1.0 s
0…250 s
10 s
Under
Generated
kVAR ➐
Disabled
-32767…0
0.1…25.0 s
1.0 s
0…250 s
10 s
Over Generated
kVAR ➐
Disabled
-32767…0
0.1…25.0 s
1.0 s
0…250 s
10 s
Under Power
kVA ➐
Disabled
0…32767
0.1…25.0 s
1.0 s
0…250 s
10 s
Over Power kVA
➐
Disabled
0…32767
0.1…25.0 s
1.0 s
0…250 s
10 s
Under Power
Factor Lagging
➐
Disabled
-100…0
-90
0.1…25.0 s
1.0 s
0…250 s
10 s
Over Power
Factor Lagging
➐
Disabled
-100…0
-95
0.1…25.0 s
1.0 s
0…250 s
10 s
Under Power
Factor Leading
➐
Disabled
0...100
90
0.1…25.0 s
1.0 s
0…250 s
10 s
Over Power
Factor Leading
➐
Disabled
0...100
95
0.1…25.0 s
1.0 s
0…250 s
10 s
Table 3: Trip Summary
Trip
Function
Trip
Enable
Factory
Default
Trip Level Settings
Trip Delay Settings
Inhibit Time
Settings ➊
Range Default
Range
Default
Range
Default