Rockwell Automation 193/592-EC1/EC3/EC5 E3 and E3 Plus Solid-State Overload Relay - Quick Reference User Manual
Page 19

19
Publication 193-QR003B-EN-P - October 2009
Protective Trip/Warning Summaries & Parameter Group Listing
(Cat. Nos. 193/592-EC1/EC2/EC3/EC5)
Table 3: Trip Summary
Trip
Function
Trip
Enable
Factory
Default
Trip Level Settings
Trip Delay Settings
Inhibit Time
Settings ➊
Range Default
Range
Default
Range
Default
Overload
Enabled
➋
➋
Trip Class
5…30
Trip Class
10
—
—
Phase Loss
Enabled
➌
➌
0.1…25.0 s
1.0 s
0…250 s
0 s
Ground Fault
(193/592-EC2)
Disabled
Internal 1…5 A
2.5 A
0.0…25.0 s
0.5 s
0…250 s
10 s
Ground Fault
(193/592-EC3)
Disabled
External
0.02…5 A ➍
2.5 A
0.0…25.0 s
0.5 s
0…250 s
10 s
Stall
Disabled
100…600% ➎
600% ➎
0…250 s
➎
10 s➎
—
—
Jam
Disabled
50…600%
250%
0.1…25.0 s
5.0 s
0…250 s
10 s
Underload
Disabled
10…100% FLA
➏
50%
0.1…25.0 s
5.0 s
0…250 s
10 s
PTC
Disabled
—
—
—
—
—
—
Current
Imbalance
Disabled
10…100%
35%
0.1…25.0 s
5.0 s
0…250 s
10 s
Comm Fault
Enabled
—
—
—
—
—
—
Comm Idle
Disabled
—
—
—
—
—
—
Remote Trip
Disabled
—
—
—
—
—
—
Voltage Input
Module
Hardware Fault
➐
Disabled —
—
—
—
—
—
Undervoltage
L-L ➐
Disabled
0...65535
100
0.1…25.0 s
1.0 s
0…250 s
10 s
Overvoltage L-L
➐
Disabled
0...65535
500
0.1…25.0 s
1.0 s
0…250 s
10 s
Voltage
Unbalance ➐
Disabled
0…100
75
0.1…25.0 s
1.0 s
0…250 s
10 s
Phase Rotation
➐
Disabled 1…2
1
—
—
0…250 s 10 s
Under
Frequency ➐
Disabled
0…250
57
0.1…25.0 s
1.0 s
0…250 s
10 s
Over Frequency
➐
Disabled
0…250
63
0.1…25.0 s
1.0 s
0…250 s
10 s
Under Real
Power ➐
Disabled
0…32767
0.1…25.0 s
1.0 s
0…250 s
10 s
Over Real
Power ➐
Disabled
0…32767
0.1…25.0 s
1.0 s
0…250 s
10 s