Appendix b, Parameter list, Serial converter parameters – Rockwell Automation 1203-SSS Smart Self-powered Serial Converter User Manual
Page 37: Serial converter, Parameters, Bserial converter parameters, Appendix
Appendix
B
Serial Converter Parameters
This chapter presents information about the parameters in the serial
converter.
Parameter List
No.
Name and Description
Details
01
[Adapter Port]
Port on the host product to which the serial converter is
connected.
Default:
0
Minimum:
0
Maximum:
7
Type:
Read Only
02
[DF1 Addr Cfg]
DF1 node address for the serial converter. This is a
decimal value.
Default:
1
Minimum:
0
Maximum:
254
Type:
Read/Write
Reset Required: Yes
03
[DF1 Rate Cfg]
Serial port rate for the DF1 serial port on the serial
converter.
Default:
0 = 9600
Values:
0 = 9600
1 = 19.2K
2 = 38.4K
Type:
Read/Write
Reset Required: Yes
04
[Comm Flt Action]
Action that the serial converter and product take if the
serial converter detects that DF1 serial
communications are disrupted. This setting is effective
only if control I/O is transmitted through the serial
converter.
Default:
0 = Fault
Values:
0 = Fault
1 = Stop (DPI) or
Fault (SCANport)
2 = Zero Data
3 = Hold Last
Type:
Read/Write
Reset Required: No
!
ATTENTION: Risk of injury or equipment damage exists. Parameter 04 -
[Comm Flt Action] lets you determine the action of the serial converter and
connected product if communications are disrupted. By default, this
parameter faults the product. You can set this parameter so that the product
continues to run. Precautions should be taken to ensure that the setting of
this parameter does not create a hazard of injury or equipment damage.