beautypg.com

Rockwell Automation 20P PowerFlex DC Drive - Frame A SCR Modules for Drive w/Power Traces Circuit Board User Manual

Powerflex, Installation instructions, What this kit includes

background image

Installation Instructions

PowerFlex

®

DC Drive - Frame A SCR Modules

for Drives with a Power Traces Circuit Board

What This Kit Includes

SCR modules (3 for non-regenerative drives, 6 for regenerative drives)

Mounting screws and washers (6 for non-regenerative drives, 12 for
regenerative drives)

Gate leads (6 for non-regenerative drives, 12 for regenerative drives)

Thermal Grease

Static strap

Important: The SCR Modules supplied with this kit should only be used in

the following Frame A drives:

!

ATTENTION: Only qualified personnel familiar with DC
drives and associated machinery should plan or implement the
installation, start-up and subsequent maintenance of the system.
Failure to comply may result in personal injury and/or equipment
damage.

!

ATTENTION: To avoid an electric shock hazard, ensure that all
power to the drive has been removed before performing the
following.

!

ATTENTION: This drive contains ESD (Electrostatic
Discharge) sensitive parts and assemblies. Static control
precautions are required when installing, testing, servicing or
repairing this assembly. Component damage may result if ESD
control procedures are not followed. If you are not familiar with
static control procedures, reference A-B publication 8000-4.5.2,
“Guarding Against Electrostatic Damage” or any other
applicable ESD protection handbook.

230V AC Input

460V AC Input

Drive Current
Rating Code

DC Amps

AC Line
Amps

HP

Drive Current
Rating Code

DC Amps

AC Line
Amps

HP

7P0

7

5.7

1.5

4P1

4.1

3.3

2

9P0

9

7.4

2

6P0

6

4.9

3

012

12

9.8

3

010

10

8.2

5

020

20

16

5

014

14

11.4

7.5

029

29

24

7.5

019

19

15.5

10

038

38

31

10

027

27

22.1

15

055

55

45

15

035

35

28.6

20

045

45

36.8

25

052

52

42.5

30