Horizontal high output – Titus Horizontal High Output IOM User Manual
Page 5
HORIZONTAL HIGH OUTPUT
HH-IOM-00 01-19-09
INSTALLATION AND
MAINTENANCE INSTRUCTIONS
6
f
o
5
e
g
a
P
9.5
Strainer (Optional)
The frequency that the strainer has to be cleaned depends on the overall conditions of
the distribution piping system. However, frequent cleaning is recommended during the
installation and start-up stages and thereafter at every season change
(Summer/Winter).
9.5.1
Open the clean-out cap on the strainer to release the dirt. Close it once clear liquid is
observed.
9.6
Pete’s Plug (Optional)
The plug is installed as an aid in measuring pressure and temperature.
9.7
Electric Heater(s) (Optional)
The heater is fastened to the fan deck at the blower outlet with sheet metal screws.
In case of heater failure, follow the procedure described below:
9.7.1
Disconnect all power sources before attempting to open the unit. Check all electrical
wiring to ensure the unit is fully isolated.
9.7.2
Unscrew the fan deck and expose the heater(s).
9.7.3
If the thermal cut-out switch is defective, disconnect the electrical wires and unscrew
it from the heater assembly. Obtain a replacement from TITUS and reinstall.