Horizontal high output, Electrical, Filter (hhe & hhp) – Titus Horizontal High Output IOM User Manual
Page 2
HORIZONTAL HIGH OUTPUT
HH-IOM-00 01-19-09
INSTALLATION AND
MAINTENANCE INSTRUCTIONS
6
f
o
2
e
g
a
P
4.
ELECTRICAL
4.1
All electrical connections are to be made in accordance with the National Electric
Code, state and local codes, bylaws, ordinances or the authority having jurisdiction.
Make all electrical connections inside the internal electric junction box by carefully
following the wiring diagram.
4.2
Electrical wiring diagram is located inside the unit’s enclosure. Adhere strictly to it in
order to avoid damage and/or personal injury.
4.3
When the thermostat and fan switch are field supplied, the following are the minimum
electrical ratings:
- Thermostat (valve load) = 0.1A @ 115V
(0.05A @ 230V)
- Fan Motor(s) @ full load amps, FLA (@115V):
*Note: Units are equipped with two (2) motors; full load amperage listed is per motor.
4.4
Where electric heating is provided with the unit (optional), an external HEAT/COOL
changeover switch has to be installed – normally wall mounted together with the fan
speed selector switch. At minimum, this switch should be rated: 10A @ 115V (5A @
230V).
Follow the wiring diagram for correct installation.
5.
FILTER (HHE & HHP)
The filter is secured to the access panel with a filter-retaining clip. To install filter, slip
filter into the filter rack and fasten it with the filter retainer clip.
SIZE
FLA (Amps)
06
3.6
08
4.3
10
4.3
12
5.1
14*
4.2
16*
4.4
18*
4.6
20*
4.5
HHC & HHE
SIZE
FLA (Amps)
06
3.5
08
3.9
10
4.1
12
4.9
14*
4.1
16*
4.2
18*
4.3
20*
4.5
HHP