HORIZONTAL HIGH OUTPUT
HH-IOM-00 01-19-09
INSTALLATION AND
MAINTENANCE INSTRUCTIONS
6
f
o
3
e
g
a
P
6.
GENERAL PRECAUTIONS
After completing the installation, recheck the following:
6.1
The drain pans, fans and motors are clean of all foreign material.
6.2
All electric wiring is properly routed, secure and capped.
6.3
The filter, where provided, is clean and secured in its position.
7.
INITIAL START-UP
7.1
Chilled/Hot Water Unit
7.1.1
Ensure that the main distribution system is operable (i.e. both supply and return piping
are under full operating pressure).
7.1.2
Open the unit’s isolating ball valves (optional) and observe that no leaks are evident.
7.1.3
Open the 2-Way or 3-Way Valve (optional) manually by turning the manual override
to the open position on the valve actuator thus pressurizing the unit’s coil.
7.1.4
Remove the cap of the air-vent valve and depress the needle to release the trapped air.
Continue until only liquid is coming through and then re-cap and secure tightly.
8.
OPERATION AND CONTROL
8.1
The unit is wired to operate with a four-position fan selector switch:
OFF
HI
High fan speed
MED
Medium fan speed
LO
Low fan speed
8.2
An external thermostat (normally wall mounted) is used to select the desired room
temperature.
8.3
Where the unit is provided with electric heating (optional), the external HEAT/COOL
changeover switch has to be set in the HEAT position to enable the thermostat to
switch the heater ON when the room temperature drops below the set point.