Hepa, Kit installation manual – Titus HEPAlert IOM for RadiaTec Diffusers User Manual
Page 4
HEPA
LERT
Kit Installation Manual
IOM-HEPA-RT-00
725343-01
09-30-04
4 of 7
16.
Secure a class 2 – 120 Vac to 24 Vac transformer
(rated for 40 VA. Transformer supplied by others.)
to back pan using self-tapping screws (see Figure
10).
17.
Connect spade-tongue terminal of 14-inch red wire
assembly to terminal barrier strip across from
previously connected red wire (see Figure 11).
18.
Connect spade-tongue terminal of 14-inch white
wire assembly to terminal barrier strip across from
previously connected white wire (see Figure 11).
19.
Feed quick-connect terminals of red and white wire
assemblies through grommet in side of base
bracket. Connect to transformer (see Figure 11).
NOTE: A single transformer may be used to
power multiple HEPAlert
TM
Kits. The 60-inch
red and white wire assemblies are supplied to
interconnect terminal barrier strips of
HEPAlert
TM
Kits on adjacent diffusers.
20.
Place and align top cover to base bracket and
secure using self-tapping screws to secure (see
Figure 12).
21.
Connect AC supply power wires to transformer
(see Figure 13).
22.
Install clean HEPA filter with wing nuts. Restore the
face screen to diffuser.
Note: Refer to RadiaTec Installation Manual
available on www.Titus-hvac.com
Note: Use a Class 2 – 120 Vac to 24 Vac transformer
(rated for 40 VA).
Figure 10. Transformer Placement
Figure 11. HEPA
LERT
Kit and Transformer Wiring
Figure 12. Securing Top Cover
Figure 13. Power Cord Connection