Bac-8001 draft222_24, Setting temperature setpoints – Titus Alpha BAC-8001/BAC-8201 Cooling Only User Manual
Page 20
Setting up VAV controllers
Setting temperature setpoints
20
Setting
temperature
setpoints
The space temperate setpoints listed in Table 3-1, “Temperature setpoints,” on
page 24 are used to control the controller VAV operation. The temperature
setpoints have default values, but may be manipulated depending on which
type of wall sensor is connected to the controller.
Occupied cooling and heating setpoints These setpoints are user controlled
space setpoints that originate from an attached sensor. If no sensor is attached
the values for these setpoints are manually entered by a controls technician.
Unoccupied cooling and heating setpoints The unoccupied setpoints are
manually entered values to set the heating and cooling temperature when the
space is unoccupied.
Minimum cooling setpoint A manually entered value to limit the occupied
cooling setpoint regardless of the value entered by the user.
Maximum heating setpoint A manually entered value to limit the occupied
heating setpoint regardless of the value entered by the user.
Minimum setpoint differential Sets the minimum temperature separation
between occupied heating and cooling setpoints.
Standby differential This differential is added or subtracted from the occupied
temperature setpoints to calculate the standby setpoints.
SAT changeover temperature Sets the supply air temperature at which the
controller will change from heating to cooling. The changeover takes place when
the supply air temperature is 2° above or below the discharge air temperature
setpoint.
Table 3-1 Temperature setpoints
Object
Description
Name
Default
AV5
Occupied Cooling Setpoint
OCC CL STPT
74°F
AV6
Occupied Heating Setpoint
OCC HT SPT
70°F
AV7
Unoccupied Cooling Setpoint
UNOCC CL STPT
80°F
AV8
Unoccupied Heating Setpt
UNOCC HT STPT
64°F
AV9
Minimum Cooling Setpt
MIN CL STPT
70°F
AV10
Maximum Heating Setpoint
MAX HT STPT
76°F
AV11
Minimum Setpoint Differential
MIN STPT DIFF
4°F
AV12
Standby Differential
STBY DIFF
3°F
AV37
SAT Changeover Temp
SAT CHANGEOVER
75°F