Thermal Transfer Systems M3-VG User Manual
Page 14

How to contact Alfa Laval
Contact details for all countries
are continually updated on our website.
Please visit www.alfalaval.com to
access the information direct.
PCT00038EN 0904
STAndArd mATeriALS
Frame plate
Mild steel, Epoxy painted
nozzles
Carbon steel
Metal lined: Stainless steel, Titanium
Rubber lined: Nitrile, EPDM
Plates
Stainless steel Alloy 316, Alloy C276, Alloy 254 SMO or
Titanium
Gaskets
Nitrile or EPDM
TecHnicAL dATA
Pressure vessel codes Ped, ASme, pvcALS™
mechanical design pressure (g) / temperature
FMS PED, pvcALS™
1.0 MPa / 180°C
FGS PED, pvcALS™
1.6 MPa / 180°C
FGS ASME
150 psig / 350°F
FG PED, pvcALS™
1.6 MPa / 180°C
FG ASME
150 psig / 350°F
FD PED, pvcALS™
2.5 MPa / 180°C
FD ASME
300 psig / 350°F
FS ASME
400 psig / 350°F
connecTionS
FMS PED
Size 200/250 mm DIN 2501 PN10,
ASME Cl. 150
FMS pvcALS™
Size 200/250 mm DIN 2501 PN10,
ASME Cl. 150, JIS 10K
FGS PED
Size 200 mm
DIN 2501 PN16,
ASME Cl. 150
FGS pvcALS™
Size 200/250 mm DIN 2501 PN16,
ASME Cl. 150, JIS 16K
FGS ASME
Size 8”
ASME Cl. 150
FG PED
Size 200/250 mm DIN 2501 PN16,
ASME CI. 150
FG pvcALS™
Size 200/250 mm DIN 2501 PN16,
ASME Cl. 150, JIS 16 K
FG ASME
Size 8”/10”
ASME Cl.150
FD PED
Size 200/250 mm DIN 2501 PN25,
ASME Cl. 300
FD ASME
Size 8”/10”
ASME Cl. 300
FS ASME
Size 8”/10”
ASME Cl. 400
maximum heat transfer surface
940 m
2
(10.000 sq. ft)
Alfa Laval reserves the right to change specifications without prior notification.
439 (17.3”)
W
1585 - 5185 (62”-204”)
1939
(76.3”)
H
h
Flow principle of a plate heat exchanger
Particulars required for quotation
– Flow rates or heat load
– Temperature program
– Physical properties of liquids in question (if not water)
– Desired working pressure
– Maximum permitted pressure drop
– Available steam pressure
measurements mm (inch)
Type
H
W
h
MX25-FMS
2595 (102”)
920 (36.2”)
325 (12.8”)
MX25-FGS
2595 (102”)
920 (36.2”)
325 (12.8”)
MX25-FG
max 3100 (122”)
920 (36.2”)
435 (17.1”)
MX25-FD
max 3100 (122”)
940 (37”)
435 (17.1”)
MX25-FS
max 3100 (122”)
940 (37”)
435 (17.1”)
The number of tightening bolts may vary depending on the
pressure rating
dimensions
THERMAL TRANSFER SYSTEMS, INC.