Plate heat exchanger

Applications

General heating and cooling duties. Heating by means
of steam.

Standard design

The plate heat exchanger consists of a pack of corrugated
metal plates with portholes for the passage of the two fluids
between which heat transfer will take place.

The plate pack is assembled between a fixed frame plate and
a movable pressure plate and compressed by tightening bolts.
The plates are fitted with a gasket which seals the interplate
channel and directs the fluids into alternate channels. The
number of plates is determined by the flow rate, physical
properties of the fluids, pressure drop and temperature
program. The plate corrugations promote fluid turbulence and
support the plates against differential pressure.

The plate and the pressure plate are suspended from an upper
carrying bar and located by a lower guiding bar, both of which
are fixed to a support column.

Connections are located in the frame plate or, if either or both
fluids make more than a single pass within the unit, in the
frame and pressure plates.

Typical capacities

Liquid flow rate
Up to 190 kg/s, depending on media, permitted pressure
drop and temperature program.

Water heating by steam
2.5 – 15 MW at a steam condensation temperature of 150°C
2.5 – 9 MW at a steam condensation temperature of 120°C

Plate types
TS20M plates

Frame types
FG and FS